D-500 MK2 User Manual Firmware V-6.3
- 24 -
The unit offers 6 digital outputs with programmable function, selectable from list.
Structure:
Negative pulling protected semiconductor output. One terminal is
connected to battery negative.
Max continuous current:
1.0 ADC
Max switching voltage:
33 VDC
Overvoltage protection:
40 VDC
Short circuit protection:
> 1.7 ADC
Reverse voltage
protection:
500 VDC
Structure:
Relay output, normally closed contact. One terminal is internally
connected to mains phase L1 input.
Max switching current:
12A @250VAC
Max switching voltage:
440VAC
Max switching power:
3000VA
Structure:
Relay output, normally open contact. One terminal is internally
connected to genset phase L1 input.
Max switching current:
16A @250VAC
Max switching voltage:
440VAC
Max switching power:
4000VA
3.10. GENERATOR CONTACTOR OUTPUT
3.9. MAINS CONTACTOR OUTPUT
3.8. DIGITAL OUTPUTS
Summary of Contents for D-500 MK2
Page 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...