D-500 MK2 User Manual Firmware V-6.3
- 175 -
The recording period is adjustable between 2 seconds and 18 hours by program parameter.
A short period will give better resolution, but it will generate more data in the memory card.
One data record is typically 250 bytes long, thus with a minimum period of 2 seconds, the unit will store
10.8 MB of data per day (250x30x60x24). A typical memory of 4GB will store data during 370 days, more
than 1 year.
With a recording period of 1 minute, 4GB memory card will store data during 30 years.
Below parameters are recorded:
Date and time of recording
Operating mode
Mains voltage phase L1 to neutral
Mains voltage phase L2 to neutral
Mains voltage phase L3 to neutral
Mains voltage phase L1-L2
Mains voltage phase L2-L3
Mains voltage phase L3-L1
Mains frequency
Mains current phase L1
Mains current phase L2
Mains current phase L3
Mains average current
Mains frequency
Mains kW phase L1
Mains kW phase L2
Mains kW phase L3
Mains total kW
Mains kVA phase L1
Mains kVA phase L2
Mains kVA phase L3
Mains kVAr phase L1
Mains kVAr phase L2
Mains kVAr phase L3
Mains pf phase L1
Mains pf phase L2
Mains pf phase L3
Mains total pf
Mains neutral current
Gen voltage phase L1 to neutral
Gen voltage phase L2 to neutral
Gen voltage phase L3 to neutral
Gen average voltage phase to neutral
Gen voltage phase L1-L2
Gen voltage phase L2-L3
Gen voltage phase L3-L1
Gen current phase L1
Gen current phase L2
Gen current phase L3
Gen average current
Gen frequency
Gen kW phase L1
Gen kW phase L2
Gen kW phase L3
Gen total kW
Gen kVA phase L1
Gen kVA phase L2
Gen kVA phase L3
Gen kVAr phase L1
Gen kVAr phase L2
Gen kVAr phase L3
Gen pf phase L1
Gen pf phase L2
Gen pf phase L3
Gen total pf
Neutral current
Oil pressure (bar & psi)
Coolant temperature (°C & °F)
Fuel level (%)
Oil temperature (°C & °F)
Canopy temperature (°C & °F)
Engine speed (rpm)
Battery voltage
Charge input voltage
Engine hours
33.4. RECORDED DATA LIST, RECORD PERIOD
Summary of Contents for D-500 MK2
Page 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...