D-500 MK2 User Manual Firmware V-6.3
- 44 -
The same unit provides different functionalities through parameter setting. Thus a single stock item will
fulfill various duties, minimizing stock cost.
The selection of the functionality is done through Controller Parameter, as shown in below picture.
CTs may be placed at alternator or load sides. The CT location selection is configured with
Controller
Configuration > CT Location
parameter. When CTs are located at the alternator side, then mains
current and power parameters will not be displayed. When CTs are located at load side, then both mains
and genset currents and power parameters will be displayed, based on contactor positions. Please review
AMF functionality connection diagrams for CT connection details.
6.1. CT LOCATION SELECTION
6. FUNCTIONALITIES
Controller
Configuration
Parameters
Selection of
Functionality
CT Location
Selection