D-500 MK2 User Manual Firmware V-6.3
- 81 -
STOPPING THE ENGINE:
Press STOP
button
STARTING THE ENGINE:
Press MAN
and then RUN
button
MANUAL LOAD TRANSFER:
Use MAINS
and GENSET
buttons.
LOAD TEST:
Press TEST
button. The genset will run and take the load.
AUTOMATIC OPERATION:
Press AUTO
button. Check that
AUTO READY
led is illuminated.
The STOP mode is entered by pressing the
button.
In this mode, the genset will be in a rest state. If it is running, then it will be stopped.
If the engine fails to stop after the expiration of
Stop Timer
then a
Fail to Stop
warning will occur.
If a
Remote Start
or
Force to Start
signal arrives in STOP mode, the genset will not start until AUTO mode
is selected.
▪
AMF Mode:
If the genset is running under load, then it will ramp out (if applicable) then the genset
contactor will open. The engine will continue to run during
Cooldown Timer
and will stop afterwards.
If the STOP button is pressed during cooldown, then the engine will immediately stop. The mains
contactor will be energized only if mains phase voltages and frequency are within the programmed
limits. If enabled, the mains phase order is also checked.
▪
Synchronizing & Load Sharing Mode:
If the genset is running under load, then it will ramp out then
the genset contactor will open. The engine will continue to run during
Cooldown Timer
and will stop
afterwards. If the STOP button is pressed during cooldown, then the engine will immediately stop.
▪
ATS Mode:
The controller will clear the REMOTE START signal output and open immediately the
genset contactor. The mains contactor will be energized only if mains phase voltages and frequency
are within the programmed limits. If enabled, the mains phase order is also checked.
Mode can be changed anytime without negative effect.
Changing the operation mode while the genset is running will
result into a behavior suitable for the new operating mode.
14.2. STOP MODE
14.1. QUICK START GUIDE
14. OPERATION OF THE UNIT
Summary of Contents for D-500 MK2
Page 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...