D-500 MK2 User Manual Firmware V-6.3
- 101 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
E-mail on IP Change
-
0
1
0
This parameter controls e-mail sending
when IP address of GPRS or ethernet
connection is changed. No warnings
generated.
0:
no e-mail on IP change
1:
e-mail sent on IP change
Fuel Pump Low Limit
%
0
100
20
If the fuel level measured from the
sender input falls below this level, then
the FUEL PUMP function will become
active.
Fuel Pump High Limit
%
0
100
80
If the fuel level measured from the
sender input goes above this level, then
the FUEL PUMP function will become
passive.
Warning Before Start
-
0
1
1
This parameter controls the activation of
the ALARM output
during “Engine Start
Delay” timer before engine run.
0:
no warning before start
1:
warning before start
Latch all Warnings
-
0
1
0
0:
warnings are latching/non-latching on
parameter control
1:
all warnings are latched. Even if the
fault source is removed, warnings will
persist until manually reset.
Remote Control Enable
-
0
1
1
This parameter controls remote control
of the unit through Rainbow, Modbus
and Modbus TCP/IP.
0:
remote control disabled
1:
remote control enabled
Annunciator Mode
-
0
1
0
0:
normal operation
1:
the unit becomes an annunciator of
the remote unit. Engine/genset control
functions are disabled.
CT Location
-
Genset
Load
Genset
0:
CTs are at the genset side. Mains
currents are not measured.
1:
CTs are at load side. Both mains and
genset currents are monitored following
contactor status.
Reverse CT Direction
-
0
1
0
This parameter is useful to invert all CT
polarities at the same time.
0:
normal CT polarity assumed.
1:
reverse CT polarity assumed.
Buzzer Enable
-
0
1
0
Internal buzzer control
0: buzzer disabled
1: buzzer enabled
Log Record Period
sec
5
3600
5
This parameter adjusts the data logging
frequency to micro-SD or USB Flash
memories. Frequent recording will
require more memory capacity.
With a period of 2 seconds, 4GB per
year of memory is necessary.
With a period of 1 minute, 133MB is
consumed per year.
17.1. CONTROLLER CONFIGURATION GROUP (continued)
Summary of Contents for D-500 MK2
Page 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...