Below is a basic list of FMI codes.
Please be aware that these codes may differ slightly depending on the engine brand and model.
FMI
DESCRIPTION
0
Value too high” Valid data, but above the normal working range
1
“Value too low” Valid data, but below the normal working range
2
“Faulty data” Intermittent or faulty data or
Short circuit to battery voltage, injector high voltage side
3
“Electrical fault” Abnormally high voltage or short circuit to battery
voltage, injector low voltage side
4
“Electrical fault” Abnormally low voltage or short circuit to battery
negative, injector low voltage or high voltage side
5
“Electrical fault” Abnormally low current or open circuit
6
“Electrical fault” Abnormally high current or short circuit to battery
negative
7
“Mechanical fault” Faulty response from mechanical system
8
“Mechanical or electrical fault” Abnormal frequency
9
“Communication fault” Abnormal updating rate or
Open circuit in injector circuit
10
“Mechanical or electrical fault” Abnormally large variations
11
“Unknown fault” Unidentified fault
12
“Component fault” Faulty unit or component
13
“Faulty calibration” Calibration values outside the limits
14
“Unknown fault” Special instructions
15
Data valid but above normal operating range - least severe level
16
Data valid but above normal operating range - moderately severe level
17
Data valid but below normal operating range - least severe level
18
Data valid but below normal operating range - moderately severe level
19
Received network data in error
20
not used (reserved)
21
not used (reserved)
22
not used (reserved)
23
not used (reserved)
24
not used (reserved)
25
not used (reserved)
26
not used (reserved)
27
not used (reserved)
28
not used (reserved)
29
not used (reserved)
30
not used (reserved)
31
Condition exist
Summary of Contents for D-500 MK2
Page 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...