D-500 MK2 User Manual Firmware V-6.3
- 139 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Voltage Up/Down
Pulse Maximum Duration
msec
0
2000
0
This parameter defines the maximum
pulse width in voltage pulse control mode.
If this parameter is set to zero then no
maximum pulse width is used.
Voltage Up/Down
Pulse Delay
msec
20
1000
20
This parameter defines the minimum
pulse delay between two of voltage
up/down control pulses.
Return to Mid-Point
-
0
1
0
This parameter controls the “Return to
Mid-
point” output relay function.
0: no return to mid-point output
1: return to mid-point output active during
stop timer.
Reactive Load Sharing
Pulse Period
msec
0
5000
10
In reactive load sharing, this is the period
between two voltage up/down pulses.
Reactive Load Sharing
Start Limit
%
0
100
0.0
This is the minimum reactive power
percentage in order to activate voltage
up/down pulses.
Summary of Contents for D-500 MK2
Page 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...