8.1.11 Wiring Configuration for a Relay Set-up with Smart Logic Control
Table 89: Wiring Configuration for a Relay with Smart Logic Control
Parameters
R1
R 2
e3
0b
u0
92
.1
1
XD2.21
XD2.22
XD2.23
XD2.24
XD2.25
XD2.26
Function
Setting
Parameter 4-30 Motor Feedback Loss Function
[1] Warning
Parameter 4-31 Motor Feedback Speed Error
100 RPM
Parameter 4-32 Motor Feedback Loss Timeout
5 s
Parameter 7-00 Speed PID Feedback Source
[2] MCB 102
Parameter 17-11 Resolution (PPR)
1024*
Parameter 13-00 SL Controller Mode
[1] On
Parameter 13-01 Start Event
[19] Warning
Parameter 13-02 Stop Event
[44] Reset key
Parameter 13-10 Comparator Operand
[21] Warning no.
Parameter 13-11 Comparator Operator
[1] ≈ (equal)
*
Parameter 13-12 Comparator Value
90
Parameter 13-51 SL Controller Event
[22] Comparator 0
Parameter 13-52 SL Controller Action
[32] Set digital out A low
Parameter 5-40 Function Relay
[80] SL digital output A
*=Default value
Notes/comments:
If the limit in the feedback monitor is exceeded,
warning 90, Feedback Mon.
is issued. The SLC
monitors
warning 90, Feedback Mon.
and if the warning becomes true, relay 1 is triggered. Exter-
nal equipment may require service.
However, if the feedback error goes below the limit again within 5 s and the warning disap-
pears, press [Reset] on the LCP.
8.1.12 Wiring Configuration: Compressor
The SmartStart guides the user through the set-up of a refrigeration compressor asking for input data about the compressor and the
refrigeration system on which the drive is running. All terminology and units used within the SmartStart are common refrigeration
type and set up is thus completed in 10–15 easy steps using just 2 keys of the LCP.
AQ357954340588en-000201 / 130R0881
114 | Danfoss A/S © 2020.09
Wiring Configuration Examples
VLT® Refrigeration Drive FC 103
Operating Guide