Character posi-
tion
Code Description
AP
Extended I/O ter cabinet heater
AQ
Extended I/O ter motor heater control
AR
Extended I/O ter insulation monitor
AS
Extended I/O ter cabinet motor heater control
AT
Extended I/O ter cabinet insulation monitor
AU
Extended I/O ter cabinet motor heater c insulation monitor
AV
Extended I/O ter motor heater c insulation monitor
The extended I/O terminal option includes 25 control terminals (-XDW) in the control compartment for use by the customer. If the
enclosed drive is configured with any option C1 card, the -XDW terminal block is used for the option C1 card wiring.
5.7.6.6 Cabinet Heater
Table 59: Auxiliary Function Type Codes
Character posi-
tion
Code Description
23–24
A3
Cabinet heater
AB
AC cabinet light + cabinet heater
AE
AC cabinet light + extended I/O ter cabinet heater
AH
AC cabinet light + extended I/O ter cabinet motor heater control
AI
AC cabinet light + extended I/O ter cabinet insulation monitor
AK
AC cabinet light + extended I/O ter cabinet motor heater c insula-
tion monitor
AL
AC cabinet light + cabinet motor heater control
AM
AC cabinet light + cabinet insulation monitor
AN
AC cabinet light + cabinet motor heater c insulation monitor
AP
Extended I/O ter cabinet heater
AS
Extended I/O ter cabinet motor heater control
AT
Extended I/O ter cabinet insulation monitor
AU
Extended I/O ter cabinet motor heater c insulation monitor
AW
Cabinet motor heater control
A8
Cabinet insulation monitor
AY
Cabinet motor heater c insulation monitor
The cabinet heater option increases the inside temperature of the cabinet above the ambient temperature, preventing condensa-
tion in the cabinet. Each cabinet has 1 cabinet heater. The heater element is self regulating. The external supply is connected to
terminal -XD1.1. When the drive is not in run state, the control relay -QAM changes the supply to the output terminals (-XD4). When
the drive is in run state, the control relay disconnects the supply to the cabinet heater. The function is disabled when MCB –FCE is
open.
AQ357954340588en-000201 / 130R0881
78 | Danfoss A/S © 2020.09
Electrical Installation
VLT® Refrigeration Drive FC 103
Operating Guide