FC 102
N110
N132
N160
N200
N250
N315
Drive module power loss at 460 V
[W]
(1)(2)(3)
2261
2724
3628
3569
4566
5714
Drive efficiency
(2)
0.98
0.98
0.98
0.98
0.98
0.98
Output frequency [Hz]
(4)
0–590
0–590
0–590
0–590
0–590
0–590
Heat sink overtemperature trip [°C
(°F)]
110 (230)
110 (230)
110 (230)
110 (230)
110 (230)
110 (230)
Control card overtemperature trip
[°C (°F)]
75 (167)
75 (167)
75 (167)
80 (176)
80 (176)
80 (176)
PHF overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
dU/dt filter overtemperature trip
[°C (°F)]
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
Sine-wave filter overtemperature
trip [°C (°F)]
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
1
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to dimension-
ing of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power
consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-efficiency-direc-
tive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each
add only 4 W.
2
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency
class, see the
Ambient Conditions
section. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
3
See also
Input Power Option Losses
section.
4
If using an output filter, the output frequency is limited further. See the
Motor Output (U, V, W)
section.
Table 97: Electrical Data, Mains Supply 3x380–480 V AC
FC 102
N355
N400
N450
N500
N560
Normal overload
110% torque for a duration of 60 s.
NO
NO
NO
NO
NO
Typical shaft output at 400 V [kW]
355
400
450
500
560
Typical shaft output at 460 V [hp]
500
600
600
650
750
Typical shaft output at 480 V [kW]
400
500
530
560
630
Enclosure size
E5h
E5h
E5h
E6h
E6h
Output current (3-phase)
Continuous (at 400 V) [A]
658
745
800
880
990
Intermittent (60 s overload) (at 400 V) [A] 724
820
880
968
1089
Continuous (at 460/480 V) [A]
590
678
730
780
890
Intermittent (60 s overload) (at 460/480
V) [A]
649
746
803
858
979
Continuous kVA (at 400 V) [kVA]
456
516
554
610
686
Continuous kVA (at 460 V) [kVA]
470
540
582
621
709
AQ357954340588en-000201 / 130R0881
142 | Danfoss A/S © 2020.09
Specifications
VLT® Refrigeration Drive FC 103
Operating Guide