FC 102
N500
N560
N630
N710
N800
Intermittent (60 s overload) (at 550 V) [A] 575
656
693
839
978
Continuous (at 575/690 V) [A]
500
570
630
730
850
Intermittent (60 s overload) (at 575/690
V) [A]
550
627
693
803
935
Continuous kVA (at 550 V) [kVA]
498
568
600
727
847
Continuous kVA (at 575 V) [kVA]
498
568
627
727
847
Continuous kVA (at 690 V) [kVA]
598
681
753
872
1016
Maximum input current
Continuous (at 525 V) [A]
504
574
607
735
857
Continuous (at 575/690 V) [A]
482
549
607
704
819
Maximum number and size of cables per phase
- Mains [mm
2
(AWG)]
4x127 (4x250
mcm)
4x127 (4x250
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
- Mains with disconnect [mm
2
(AWG)]
4x127 (4x250
mcm)
4x127 (4x250
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
- Mains with fusible disconnect [mm
2
(AWG)]
4x127 (4x250
mcm)
4x127 (4x250
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
- Mains with contactor [mm
2
(AWG)]
4x127 (4x250
mcm)
4x127 (4x250
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
- Motor [mm
2
(AWG)]
4x127 (4x250
mcm)
4x127 (4x250
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
4x185 (4x350
mcm)
Drive module power loss at 600 V [W]
(1)(2)
(3)
6879
8076
9208
10346
12723
Drive module power loss at 690 V [W]
(1)(2)
(3)
6715
7852
8921
10066
12321
Drive efficiency
(2)
0.98
0.98
0.98
0.98
0.98
Output frequency [Hz]
(4)
0–500
0–500
0–500
0–500
0–500
Heat sink overtemperature trip [°C (°F)]
110 (230)
110 (230)
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [°C
(°F)]
80 (176)
80 (176)
80 (176)
80 (176)
80 (176)
PHF overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
dU/dt filter overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
AQ357954340588en-000201 / 130R0881
146 | Danfoss A/S © 2020.09
Specifications
VLT® Refrigeration Drive FC 103
Operating Guide