Illustration 45: Cabinet Heater Terminals
5.7.6.7 Motor Heater Control
Table 60: Auxiliary Function Type Codes
Character posi-
tion
Code Description
23–24
A4
Motor heater control
AC
AC cabinet light + motor heater control
AF
AC cabinet light + extended I/O ter motor heater control
AH
AC cabinet light + extended I/O ter cabinet motor heater control
AJ
AC cabinet light + extended I/O ter motor heater c insulation monitor
AK
AC cabinet light + extended I/O ter cabinet motor heater c insula-
tion monitor
AL
AC cabinet light + cabinet motor heater control
AN
AC cabinet light + cabinet motor heater c insulation monitor
AO
AC cabinet light + motor heater c insulation monitor
AQ
Extended I/O ter motor heater control
AS
Extended I/O ter cabinet motor heater control
AU
Extended I/O ter cabinet motor heater c insulation monitor
AV
Extended I/O ter motor heater c insulation monitor
AW
Cabinet motor heater control
AY
Cabinet motor heater c insulation monitor
AZ
Motor heater c insulation monitor
The motor heater option provides the ability to control the supply for the motor anti-condensation heater. The 24 V DC external
supply is connected to terminal -XD1.1 in the lower part of the cabinet. When the drive is not in run state, the control relay -QAM
changes the external supply to the -XDM output terminals. When the drive is in run state, the control relay disconnects the external
supply to the motor heater. The function is disabled when MCB –FCN is open.