Table 42: Airflow Rates for E6h Enclosure
Cabinet
Back-channel fan [m
3
/hr (cfm)]
Drive module top fan [m
3
/hr (cfm)]
Cabinet door fan [m
3
/hr (cfm)]
PHF/line reactor
1285 (755)
–
–
Input options
–
–
510 (310)
Drive
1053–1206 (620–710)
629 (370)
430 (255)
dU/dt
665 (392)
–
–
Sine-wave
2x900 (530)
–
–
Top entry/top exit
–
–
–
4.9 Lifting the Drive
W A R N I N G
HEAVY WEIGHT
The drive is heavy. Failure to follow local safety regulations for lifting heavy weights may cause death, personal injury, or property
damage.
Ensure that the lifting equipment is in proper working condition.
Check the weight of the drive and verify that the lifting equipment can safely lift the weight.
Ensure that the angle from the top of the drive to the lifting cable is 65° or greater.
Test lift the drive approximately 610 mm (24 in) to verify the proper center of gravity lift point. Reposition the lifting point if
the unit is not level.
Never walk under suspended loads.
AQ357954340588en-000201 / 130R0881
38 | Danfoss A/S © 2020.09
Mechanical Installation
VLT® Refrigeration Drive FC 103
Operating Guide