FC 102
N110
N132
N160
N200
N250
N315
N400
N450
- Mains with contactor
[mm
2
(AWG)]
2x95
(2x3/0
mcm)
2x95
(2x3/0
mcm)
2x95
(2x3/0
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
4x127
(4x250
mcm)
- Motor [mm
2
(AWG)]
2x95
(2x3/0
mcm)
2x95
(2x3/0
mcm)
2x95
(2x3/0
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
4x127
(4x250
mcm)
Drive module power loss
at 600 V [W]
(1)(2)(3)
1740
2101
2649
3074
3723
4465
5028
6062
Drive module power loss
at 690 V [W]
(1)(2)(3)
1798
2167
2740
3175
3851
4614
5155
5939
Drive efficiency
(2)
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
Output frequency [Hz]
(4)
0–590
0–590
0–590
0–590
0–590
0–590
0–590
0–500
Heat sink overtempera-
ture trip [°C (°F)]
110 (230)
110 (230)
110 (230)
110 (230)
110 (230)
110 (230)
110 (230) 110 (230)
Control card overtem-
perature trip [°C (°F)]
75 (167)
75 (167)
75 (167)
75 (167)
80 (176)
80 (176)
80 (176)
80 (176)
PHF overtemperature
trip [°C (°F)]
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302) 150 (302)
dU/dt filter overtemper-
ature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302) 150 (302)
Sine-wave filter over-
temperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302) 150 (302)
1
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to dimension-
ing of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power
consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-efficiency-direc-
tive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each
add only 4 W.
2
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency
class, see the
Ambient Conditions
section. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
3
See also
Input Power Option Losses
section.
4
If using an output filter, the output frequency is limited further. See the
Motor Output (U, V, W)
section.
Table 99: Electrical Data, Mains Supply 3x525–690 V AC
FC 102
N500
N560
N630
N710
N800
Normal overload
110% torque for a duration of 60 s.
NO
NO
NO
NO
NO
Typical shaft output at 550 V [kW]
400
450
500
560
670
Typical shaft output at 575 V [hp]
500
600
650
750
950
Typical shaft output at 690 V [kW]
500
560
630
710
800
Enclosure size
E5h
E5h
E6h
E6h
E6h
Output current (3-phase)
Continuous (at 550 V) [A]
523
596
630
763
889
AQ357954340588en-000201 / 130R0881 | 145
Danfoss A/S © 2020.09
Specifications
VLT® Refrigeration Drive FC 103
Operating Guide
Summary of Contents for VLT FC 103