Table 29: EMC Filter Codes
Character position
Code
Description
36
2
(H2) RFI class A2 (C3)
4
(H4) RFI class A1 (C2)
Table 30: Reserved Code
Character position
Code
Description
37–39
X
None
Table 31: Documentation Language Codes
Character position
Code
Description
40
X
English, no 2
nd
language
G
E German
F
E French
3.5 Power Ratings, Weight, and Dimensions
Table 32: Power Ratings and Dimensions for D9h–D10h and E5h–E6h Enclosures (Standard Configurations)
Enclosed drive
D9h
D10h
E5h
E6h
Rated power at 380–480 V [kW
(hp)]
110–160 (150–
250)
200–315 (300–450)
355–450 (500–600)
500–560 (650–750)
Rated power at 525–690 V [kW
(hp)]
110–160 (125–
200)
200–400 (250–400)
450–630 (450–650)
710–800 (750–950)
Protection rating
IP21 (NEMA 1)/
IP54 (NEMA 12)
IP21 (NEMA 1)/IP54
(NEMA 12)
IP21 (NEMA 1)/IP54
(NEMA 12)
IP21 (NEMA 1)/IP54
(NEMA 12)
Drive cabinet
D9h
D10h
E5h
E6h
Height [mm (in)]
(1)
2100 (82.7)
2100 (82.7)
2100 (82.7)
2100 (82.7)
Width [mm (in)]
(2)
400 (15.8)
600 (23.6)
600 (23.6)
800 (31.5)
Depth [mm (in)]
600 (23.6)
600 (23.6)
600 (23.6)
600 (23.6)
Weight [kg (lb)]
(2)
280 (617)
355 (783)
400 (882)
431 (950)
Input filter cabinet
D9h
D10h
E5h
E6h
Height [mm (in)]
(1)
2100 (82.7)
2100 (82.7)
2100 (82.7)
2100 (82.7)
Width [mm (in)]
400 (15.8)
400 (15.8)/600 (23.6) 600 (23.6)/800 (31.5)
600 (23.6)/800 (31.5)
Depth [mm (in)]
600 (23.6)
600 (23.6)
600 (23.6)
600 (23.6)
Weight [kg (lb)]
410 (904)
410 (904)/530
(1168)
530 (1168)
530 (1168)/955
(2105)
Input power options cabinet
D9h
D10h
E5h
E6h
Height [mm (in)]
(1)
–
2100 (82.7)
2100 (82.7)
2100 (82.7)
Width [mm (in)]
–
600 (23.6)
600 (23.6)
600 (23.6)
AQ357954340588en-000201 / 130R0881 | 27