Load [%]
Automatic capacitor control [p.u.]
(1)(2)
Capacitor always connected [p.u.]
(1)
Capacitor always open [p.u.]
(1)
75
0.997
0.997
0.930
100
0.986
0.986
0.920
160
0.980
0.980
0.910
1
Positive numbers indicate lagging reactive currents. Negative numbers indicate leading currents.
2
The capacitor connecting contactor switches at 20% load.
10.7.2 Line Reactor Specifications
All line reactors are equipped with thermal switches and are looped to the enclosed drive for overtemperature protection. For more
details, refer to the
Control Compartment
section. The line reactor configuration varies depending on the enclosure and voltage re-
quired.
Table 101: Line Reactor Configuration for D9h–D10h and E5h–E6h Enclosures, 380–480 V
Enclosure
Model
Impedance [%]
D9h
N110
2.70
D9h
N132
3.22
D9h
N160
2.87
D10h
N200
3.47
D10h
N250
3.01
D10h
N315
3.65
E5h
N355
3.30
E5h
N400
3.62
E5h
N450
3.83
E6h
N500
2.94
E6h
N560
3.23
Table 102: Line Reactor Configuration for D9h–D10h and E5h–E6h Enclosures, 525–690 V
Enclosure
Model
Impedance [%)
D9h
N110
2.30
D9h
N132
2.78
D9h
N160
3.29
D10h
N200
2.92
D10h
N250
3.67
D10h
N315
3.08
D10h
N355
3.67
E5h
N400
2.89
E5h
N500
3.11
AQ357954340588en-000201 / 130R0881 | 153
Danfoss A/S © 2020.09
Specifications
VLT® Refrigeration Drive FC 103
Operating Guide