8.1.4 Wiring Configuration: Feedback
Table 76: Wiring Configuration for Analog Current Feedback Transducer (2-wire)
Parameters
4-20 mA
+24 V
D IN
D IN
D IN
COM
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
A 54
U - I
+
-
e
3
0
b
u
0
7
8
.1
0
XD2.10
XD2.11
XD2.12
XD2.13
XD2.18
XD2.14
XD2.15
XD2.16
XD2.17
XD2.19
XD2.6
XD2.7
XD2.8
XD2.9
XD2.5
XD2.4
D IN
+24 V
D IN
Function
Setting
Parameter 6-22 Terminal 54 Low Current
4 mA*
Parameter 6-23 Terminal 54 High Current
20 mA*
Parameter 6-24 Terminal 54 Low Ref./Feedb. value
0*
Parameter 6-25 Terminal 54 High Ref./Feedb. Value
50*
*=Default value
Notes/comments:
D IN 37 is an option.
Terminal 54 in the parameter title corresponds to terminal XD2.8 in the control compartment.
Table 77: Wiring Configuration for Analog Voltage Feedback Transducer (3-wire)
Parameters
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
A54
U - I
0-10 V
+
-
e
3
0
b
u
0
7
9
.1
0
XD2.10
XD2.11
XD2.12
XD2.13
XD2.18
XD2.14
XD2.15
XD2.16
XD2.17
XD2.19
XD2.6
XD2.7
XD2.8
XD2.9
XD2.5
XD2.4
Function
Setting
Parameter 6-20 Terminal 54 Low Voltage
0.07 V*
Parameter 6-21 Terminal 54 High Voltage
10 V*
Parameter 6-24 Terminal 54 Low Ref./Feedb. value
0*
Parameter 6-25 Terminal 54 High Ref./Feedb. Value
50*
*=Default value
Notes/comments:
D IN 37 is an option.
Terminal 54 in the parameter title corresponds to terminal XD2.8 in the control compartment.
AQ357954340588en-000201 / 130R0881 | 107
Danfoss A/S © 2020.09
Wiring Configuration Examples