8.1.7 Wiring Configuration: External Alarm Reset
Table 85: Wiring Configuration for External Alarm Reset
Parameter
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
e
3
0
b
u
0
8
8
.1
0
XD2.10
XD2.11
XD2.12
XD2.13
XD2.18
XD2.14
XD2.15
XD2.16
XD2.17
XD2.19
Function
Setting
Parameter 5-11 Terminal 19 Digital Input
[1] Reset
*=Default value
Notes/comments:
D IN 37 is an option.
Terminal 19 in the parameter title corresponds to terminal XD2.13 in the control compartment.
8.1.8 Wiring Configuration: RS485
Table 86: Wiring Configuration for RS485 Network Connection
Parameter
e
3
0
b
u
0
8
9
.1
0
XD2.10
XD2.11
XD2.12
-
RS485
+
Function
Setting
Parameter 8-30 Protocol
FC*
Parameter 8-31 Address
1*
Parameter 8-32 Baud Rate
9600*
*=Default value
Notes/comments:
Select protocol, address, and baud rate in the above-mentioned parameters.
D IN 37 is an option.
8.1.9 Wiring Configuration: Motor Thermistor
C A U T I O N
THERMISTOR INSULATION
Risk of personal injury or equipment damage.
Use only thermistors with reinforced or double insulation to meet PELV insulation requirements.
AQ357954340588en-000201 / 130R0881
112 | Danfoss A/S © 2020.09
Wiring Configuration Examples
VLT® Refrigeration Drive FC 103
Operating Guide