Minimum cable cross-section: 10 mm
2
(6 AWG) (or 2 rated ground wires terminated separately).
Tighten the terminals in accordance with the information provided in
EMC-compliant Installation
Refer to the
EMC-compliant Installation
section.
e
3
0
b
u
1
5
1
.1
0
7
8
9
10
3
4
5
6
1
2
Illustration 47: Different Ways of Connecting Multiple Cables to 1 Terminal
1
Cable 1
2
Cable 2
3
Connection bushing
4
Cable 1
5
Cable 2
6
Cable 3
7
Cable 1 lug
8
Bolt holder on the connector
9
Terminal connector
10
Cable 2 lug
5.8.2 Connecting to the Mains
If the enclosed drive is not configured with an input filter or input power option, connect the mains to the drive module. Otherwise,
connect the mains to the input power option.
Procedure
Strip a section of the outer cable insulation.
Fasten a connector/cable lug to the end of the stripped cable.
Create an electrical connection between the cable shield and ground by securing the stripped wire under the cable clamp.
Connect the ground wire to the nearest grounding terminal in accordance with the grounding instructions provided in
.
Connect the 3-phase AC input power cables to terminals R (L1), S (L2), and T (L3).
AQ357954340588en-000201 / 130R0881
82 | Danfoss A/S © 2020.09
Electrical Installation
VLT® Refrigeration Drive FC 103
Operating Guide