10.1.2 Electrical Data, 525–690 V AC
Table 98: Electrical Data, Mains Supply 3x525–690 V AC
FC 102
N110
N132
N160
N200
N250
N315
N400
N450
Normal overload
110% torque for a dura-
tion of 60 s.
NO
NO
NO
NO
NO
NO
NO
NO
Typical shaft output at
550 V [kW]
90
110
132
160
200
250
315
355
Typical shaft output at
575 V [hp]
125
150
200
250
300
350
400
450
Typical shaft output at
690 V [kW]
110
132
160
200
250
315
400
450
Enclosure size
D9h
D9h
D9h
D10h
D10h
D10h
D10h
E5h
Output current (3-phase)
Continuous (at 550 V)
[A]
137
162
201
253
303
360
418
470
Intermittent (60 s over-
load) (at 550 V) [A]
151
178
221
278
333
396
460
517
Continuous (at 575/690
V) [A]
131
155
192
242
290
344
400
450
Intermittent (60 s over-
load) (at 575/690 V) [A]
144
171
211
266
319
378
440
495
Continuous kVA (at 550
V) [kVA]
125
147
183
230
276
327
380
448
Continuous kVA (at 575
V) [kVA]
131
154
191
241
289
343
398
448
Continuous kVA (at 690
V) [kVA]
157
185
230
289
347
411
478
538
Maximum input current
Continuous (at 525 V)
[A]
132
156
193
244
292
347
403
453
Continuous (at 575/690
V) [A]
126
149
185
233
279
332
385
434
Maximum number and size of cables per phase
- Mains [mm
2
(AWG)]
2x95
(2x3/0
mcm)
2x95
(2x3/0
mcm)
2x95
(2x3/0
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
4x127
(4x250
mcm)
- Mains with disconnect
[mm
2
(AWG)]
2x95
(2x3/0
mcm)
2x95
(2x3/0
mcm)
2x95
(2x3/0
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
4x127
(4x250
mcm)
- Mains with fusible dis-
connect [mm
2
(AWG)]
2x95
(2x3/0
mcm)
2x95
(2x3/0
mcm)
2x95
(2x3/0
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
2x185
(2x350
mcm)
4x127
(4x250
mcm)
AQ357954340588en-000201 / 130R0881
144 | Danfoss A/S © 2020.09
Specifications
VLT® Refrigeration Drive FC 103
Operating Guide