10 Specifications
10.1 Electrical Data
10.1.1 Electrical Data, 380–480 V AC
Table 96: Electrical Data, Mains Supply 3x380–480 V AC
FC 102
N110
N132
N160
N200
N250
N315
Normal overload
110% torque for a duration of
60 s.
NO
NO
NO
NO
NO
NO
Typical shaft output at 400 V [kW]
110
132
160
200
250
315
Typical shaft output at 460 V [hp]
150
200
250
300
350
450
Typical shaft output at 480 V [kW]
132
160
200
250
315
355
Enclosure size
D9h
D9h
D9h
D10h
D10h
D10h
Output current (3-phase)
Continuous (at 400 V) [A]
212
260
315
395
480
588
Intermittent (60 s overload) (at
400 V) [A]
233
286
347
435
528
647
Continuous (at 460/480 V) [A]
190
240
302
361
443
535
Intermittent (60 s overload) (at
460/480 V) [A]
209
264
332
397
487
589
Continuous kVA (at 400 V) [kVA]
147
180
218
274
333
407
Continuous kVA (at 460 V) [kVA]
151
191
241
288
353
426
Continuous kVA (at 480 V) [kVA]
165
208
262
313
384
463
Maximum input current
Continuous (at 400 V) [A]
204
251
304
381
463
567
Continuous (at 460/480 V) [A]
183
231
291
348
427
516
Maximum number and size of cables per phase
- Mains [mm
2
(AWG)]
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
- Mains with disconnect [mm
2
(AWG)]
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
- Mains with fusible disconnect
[mm
2
(AWG)]
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
- Mains with contactor [mm
2
(AWG)]
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
- Motor [mm
2
(AWG)]
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
Drive module power loss at 400 V
[W]
(1)(2)(3)
2559
2954
3770
4116
5137
6674
AQ357954340588en-000201 / 130R0881 | 141
Danfoss A/S © 2020.09
Specifications
VLT® Refrigeration Drive FC 103
Operating Guide