3.23 Parameters 26-** Analog I/O Option
MCB 109
The VLT
®
Analog I/O Option MCB 109 extends the
functionality of VLT
®
AQUA Drive FC 202 Series frequency
converters by adding some extra, programmable analog
inputs and outputs. This is useful in control installations
where the frequency converter may be used as decentral
I/O, obviating the need for an outstation and thus reducing
cost. It also provides flexibility in project planning.
NOTICE
The maximum current for the analog outputs 0–10 V is 1
mA.
NOTICE
Where live zero monitoring is used, it is important that
any analog inputs not being used for the frequency
controller, for example being used as part of the building
management system decentral I/O, have their live zero
function disabled.
Terminal
Parameters
Analog inputs
X42/1
Parameter 26-00 Terminal X42/1
,
X42/3
Parameter 26-01 Terminal X42/3
,
X42/5
Parameter 26-02 Terminal X42/5
,
Analog outputs
X42/7
Parameter 26-40 Terminal X42/7
.
X42/9
Parameter 26-50 Terminal X42/9
.
X42/11
Parameter 26-60 Terminal X42/11
.
Analog inputs
53
Parameter group 6-1* Analog
Input 1
.
54
Parameter group 6-2* Analog
Input 2
.
Analog output
42
Parameter group 6-5* Analog
Input 1
.
Relays
Relay 1, terminals 1, 2, 3.
Parameter group 5-4* Relays
.
Relay 2, terminals 4, 5, 6.
Parameter group 5-4* Relays
.
Table 3.34 Analog Inputs
It is also possible to read the analog inputs, write to the
analog outputs, and control the relays, using communi-
cation via the fieldbus.
Terminal
Parameters
Analog inputs (read)
X42/1
.
X42/3
.
X42/5
.
Analog outputs (write)
X42/7
.
X42/9
.
X42/11
.
Analog inputs (read)
53
.
54
.
Analog output
42
Relays
Relay 1, terminals 1, 2, 3.
Relay 2, terminals 4, 5, 6.
NOTICE
Enable the relay outputs via control word bit 11 (relay
1) and bit 12 (relay 2).
Table 3.35 Analog Inputs via Fieldbus
On-board real-time clock setting
The VLT
®
Analog I/O Option MCB 109 incorporates a real-
time clock with battery back-up. This option can be used
as back-up of the standard clock function included in the
frequency converter. See
parameter group 0-7* Clock
Settings
.
Use the MCB 109 for control of devices such as actuators
or valves, using the extended closed-loop facility, thus
removing control from the existing control system. See
parameter group 21-** Extended Closed Loop
. There are 3
independent closed-loop PID controllers.
Parameter Description
Programming Guide
MG20OB02