26-42 Terminal X42/7 Max. Scale
Range:
Function:
100
%
*
[0 -
200 %]
Scale the maximum output of the selected
analog signal at terminal X42/7. Set the value to
the maximum value of the voltage signal output.
Scale the output to give a voltage lower than
10 V at full scale; or 10 V at an output below
100% of the maximum signal value. If 10 V is the
required output current at a value between 0–
100% of the full-scale output, program the
percentage value in the parameter, that is
50%=10 V. If a voltage 0–10 V is required at
maximum output, calculate the percentage as
follows:
10V
desired maximum voltage x 100 %
that is
5V : 10V
5V × 100 % = 200 %
See
26-43 Terminal X42/7 Bus Control
Range:
Function:
0 %
*
[0 - 100 %] Holds the level of terminal X42/7 if
controlled by bus.
26-44 Terminal X42/7 Timeout Preset
Range:
Function:
0 %
*
[0 -
100 %]
Holds the preset level of terminal X42/7.
If a fieldbus and a timeout function are
selected in
parameter 26-50 Terminal X42/9
, the output presets to this level.
26-50 Terminal X42/9 Output
Option:
Function:
Set the function of terminal X42/9.
[0]
*
No operation
[52]
MCO 0-20mA/
0-10V
[100] Output freq.
0-100
0–100 Hz, (0–10 V).
[101] Reference Min-
Max
Minimum reference–maximum
reference, (0–10 V).
[102] Fe-200% -200% to +200% of
parameter 3-03 Maximum Reference
, (0–
10 V).
[103] Motor cur. 0-Imax 0–inverter maximum current
parameter 16-37 Inv. Max. Current
), (0–
10 V).
[104] Torque 0-Tlim
0–torque limit (
), (0–10 V).
[105] Torque 0-Tnom
0–motor rated torque, (0–10 V).
[106] Power 0-Pnom
0–motor rated power, (0–10 V).
26-50 Terminal X42/9 Output
Option:
Function:
[107] Speed 0-HighLim 0–speed high limit
parameter 4-13 Motor Speed High Limit
and
), (0–10 V).
[108] -160%
[109] Out frq 0-Fmax
[113] Ext. Closed Loop
1
0–100%, (0–10 V).
[114] Ext. Closed Loop
2
0–100%, (0–10 V).
[115] Ext. Closed Loop
3
0–100%, (0–10 V).
[139] Bus ctrl.
0–100%, (0–10 V).
[141] Bus ctrl t.o.
0–100%, (0–10 V).
[156] Flow Rate
26-51 Terminal X42/9 Min. Scale
For more information, see
parameter 6-51 Terminal 42 Output Min
.
Range:
Function:
0 %
*
[0 -
200 %]
Scale the minimum output of the selected
analog signal at terminal X42/9 as a percentage
of the maximum signal level. For example, if 0 V
is required at 25% of the maximum output
value, program 25%. Scaling values up to 100%
can never be higher than the corresponding
setting in
parameter 26-52 Terminal X42/9 Max.
26-52 Terminal X42/9 Max. Scale
See
.
Range:
Function:
100 %
*
[0 -
200 %]
Scale the maximum output of the selected
analog signal at terminal X42/9. Set the value to
the maximum value of the voltage signal
output. Scale the output to give a voltage lower
than 10 V at full scale; or 10 V at an output
below 100% of the maximum signal value. If
10 V is the required output current at a value
between 0–100% of the full-scale output,
program the percentage value in the parameter,
that is, 50%=10 V. If a voltage 0–10 V is required
at maximum output, calculate the percentage as
follows:
5V : 10V
5V × 100 % = 200 %
26-53 Terminal X42/9 Bus Control
Range:
Function:
0 %
*
[0 - 100 %] Holds the level of terminal X42/9 if
controlled by bus.
Parameter Description
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
221
3
3