1-93 Thermistor Source
Option:
Function:
(selected in
parameter 3-15 Reference 1 Source
,
parameter 3-16 Reference 2 Source
, or
parameter 3-17 Reference 3 Source
When using VLT
®
PTC Thermistor Card MCB
112, always select
[0] None
.
[0]
*
None
[1]
Analog
Input 53
[2]
Analog
Input 54
[3]
Digital input
18
[4]
Digital input
19
[5]
Digital input
32
[6]
Digital input
33
1-95 KTY Sensor Type
Option:
Function:
Select the type of the thermistor sensor.
[0]
*
KTY Sensor 1
1 k
Ω
at 100
°
C (212
°
F).
[1]
KTY Sensor 2
1 k
Ω
at 25
°
C (77
°
F).
[2]
KTY Sensor 3
2 k
Ω
at 25
°
C (77
°
F).
1-96 KTY Thermistor Resource
Option:
Function:
Select analog input terminal 54 as a thermistor
sensor input. Terminal 54 cannot be selected as
thermistor source if otherwise used as reference
(see
parameter 3-15 Reference Resource 1
to
parameter 3-17 Reference Resource 3
).
NOTICE
Connection of thermistor sensor
between terminals 54 and 55 (GND). See
chapter 3.3.15 PTC Thermistor Connection
[0]
*
None
[2]
Analog
input 54
1-97 KTY Threshold level
Range:
Function:
80 °C
*
[-40 - 140 °C] Select the thermistor sensor threshold
level for motor thermal protection.
Parameter Description
VLT
®
AQUA Drive FC 202
62
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
3
3