Input polarity of control terminals
12
13
18
19
27
29
32
33
20
37
+24
VDC
0
VDC
130B
T106.10
PNP (Source)
Digital input wiring
Illustration 1.3 PNP (Source)
NPN (Sink)
Digital input wiring
12
13
18
19
27
29
32
33
20
37
+24
VDC
0
VDC
130B
T107.11
Illustration 1.4 NPN (Sink)
NOTICE
Control cables must be shielded/armored.
See the section
Grounding of Shielded Control Cables
in the
design guide
for the correct termination of control cables.
130BA681.10
Illustration 1.5 Grounding of Shielded/Armored Control Cables
1.9.2 Start/Stop
Terminal 18 =
Parameter 5-10 Terminal 18 Digital Input
[8]
Start.
Terminal 27 =
Parameter 5-12 Terminal 27 Digital Input [0]
No operation
(default
[2] Coast inverse
).
Terminal 37 = Safe Torque Off (where available).
12 13 18
37
130BA155.12
32
27
19
29
33 20
P 5-12 [0]
P 5-10 [8]
Start/Stop
+24V
Speed
Safe Stop
Start/Stop
[18]
Illustration 1.6 Start/Stop
Introduction
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
11
1
1