22-26 Dry Pump Function
Select the action for dry-pump operation.
Option:
Function:
[1]
Warning
NOTICE
To use dry-pump detection:
1.
Enable low-power detection in
parameter 22-21 Low Power
Detection
.
2.
Commission low-power detection
using either
parameter group
22-3* No-flow Power Tuning No
Flow Power Tuning
, or
parameter 22-20 Low Power Auto
Set-up
NOTICE
Do not set
parameter 14-20 Reset Mode
to
[13] Infinite auto reset
, when
parameter 22-26 Dry Pump Function
is set
to
[2] Alarm
. Doing so causes the
frequency converter to continuously cycle
between running and stopping when a
dry-pump condition is detected.
NOTICE
For frequency converters with constant-
speed bypass.
If an automatic bypass function starts the
bypass at persistent alarm conditions,
disable the automatic bypass function, if
[2] Alarm
or
[3] Man. Reset Alarm
is
selected as the dry-pump function.
The frequency converter continues to run, but
activates a dry-pump warning
(warning 93, Dry
pump)
. A frequency converter digital output or a
serial communication bus can communicate a
warning to other equipment.
[2]
Trip
The frequency converter stops running and
activates a dry-pump alarm
(alarm 93, Dry
pump)
. A frequency converter digital output or a
serial communication bus can communicate an
alarm to other equipment.
[3]
Manual
Reset Trip
The frequency converter stops running and
activates a dry-pump alarm
(alarm 93, Dry
pump)
. A frequency converter digital output or a
serial communication bus can communicate an
alarm to other equipment.
[4]
Stop and
Trip
22-27 Dry Pump Delay
Range:
Function:
10 s
*
[0 -
600 s]
Defines for how long the dry-pump condition
must be active before activating a warning or an
alarm.
The frequency converter waits for the no-flow
delay time (
) to
expire before the timer for the dry-pump delay
starts.
22-28 No-Flow Low Speed [RPM]
Range:
Function:
Size related
*
[ 0 - par.
4-13 RPM]
Used to set the speed for no-flow
low-speed detection.
If a low-speed detection at a speed
different from the motor minimum
speed is needed, this parameter may
be used.
22-29 No-Flow Low Speed [Hz]
Range:
Function:
Size related
*
[ 0 - par.
4-14 Hz]
Used to set the speed for no-flow
low-speed detection.
If a low-speed detection at a speed
different from the motor minimum
speed is needed, this parameter may
be used.
3.19.3 22-3* No-flow Power Tuning
If auto set-up is disabled in
, the tuning sequence is:
NOTICE
Set
parameter 1-03 Torque Characteristics
before tuning
takes place.
1.
Close the main valve to stop flow.
2.
Run with motor until the system has reached
normal operating temperature.
3.
Press [Hand On] and adjust speed for approxi-
mately 85% of rated speed. Note the exact speed.
4.
Read power consumption either by looking for
actual power in the data line in the LCP or by
viewing 1 of the following parameters:
4a
.
Or
4b
in the Main
Menu.
Note the power readout.
5.
Change speed to approximately 50% of rated
speed. Note the exact speed.
Parameter Description
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
181