13-52 SL Controller Action
Array [20]
Option:
Function:
coming from either the digital inputs or
via a fieldbus.
[18]
Select ramp 1
Selects ramp 1.
[19]
Select ramp 2
Selects ramp 2.
[22]
Run
Issues a start command to the frequency
converter.
[23]
Run reverse
Issues a start reverse command to the
frequency converter.
[24]
Stop
Issues a stop command to the frequency
converter.
[26]
DC Brake
Issues a DC stop command to the
frequency converter.
[27]
Coast
The frequency converter coasts
immediately. All stop commands
including the coast command stop the
SLC.
[28]
Freeze output
Freezes the output frequency of the
frequency converter.
[29]
Start timer 0
Starts timer 0, see
for further description.
[30]
Start timer 1
Starts timer 1, see
for further description.
[31]
Start timer 2
Starts timer 2, see
for further description.
[32]
Set digital out A
low
Any output with digital output 1
selected is low (off).
[33]
Set digital out B
low
Any output with digital output 2
selected is low (off).
[34]
Set digital out C
low
Any output with digital output 3
selected is low (off).
[35]
Set digital out D
low
Any output with digital output 4
selected is low (off).
[36]
Set digital out E
low
Any output with digital output 5
selected is low (off).
[37]
Set digital out F
low
Any output with digital output 6
selected is low (off).
[38]
Set digital out A
high
Any output with digital output 1
selected is high (closed).
[39]
Set digital out B
high
Any output with digital output 2
selected is high (closed).
[40]
Set digital out C
high
Any output with digital output 3
selected is high (closed).
[41]
Set digital out D
high
Any output with digital output 4
selected is high (closed).
13-52 SL Controller Action
Array [20]
Option:
Function:
[42]
Set digital out E
high
Any output with digital output 5
selected is high (closed).
[43]
Set digital out F
high
Any output with digital output 6
selected is high (closed).
[60]
Reset Counter A Resets counter A to 0.
[61]
Reset Counter B Resets counter B to 0.
[62]
Counter A (up)
[63]
Counter A
(down)
[64]
Counter B (up)
[65]
Counter B
(down)
[70]
Start Timer 3
Starts timer 3, see
for further description.
[71]
Start Timer 4
Starts timer 4, see
for further description.
[72]
Start Timer 5
Starts timer 5, see
for further description.
[73]
Start Timer 6
Starts timer 6, see
for further description.
[74]
Start Timer 7
Starts timer 7, see
for further description.
[80]
Sleep Mode
Starts the sleep mode.
[81]
Derag
Starts deragging (see
parameter group
29-0* Pipe Fill
for further information).
[82]
Reset Derag
Counter
[90]
Set ECB Bypass
Mode
[91]
Set ECB Drive
Mode
[100] Reset Alarms
[101] Reset Flow
Totalized
Volume Counter
[102] Reset Flow
Actual Volume
Counter
Parameter Description
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
129