4.1.17 20-** Drive Closed Loop
Param-
eter #
Parameter description
Default value
4 set-up
Change during
operation
Conversion
index
Type
20-0* Feedback
20-00
Feedback 1 Source
[2] Analog Input 54
All set-ups
TRUE
-
Uint8
20-01
Feedback 1 Conversion
[0] Linear
All set-ups
FALSE
-
Uint8
20-02
Feedback 1 Source Unit
ExpressionLimit
All set-ups
TRUE
-
Uint8
20-03
Feedback 2 Source
[0] No function
All set-ups
TRUE
-
Uint8
20-04
Feedback 2 Conversion
[0] Linear
All set-ups
FALSE
-
Uint8
20-05
Feedback 2 Source Unit
ExpressionLimit
All set-ups
TRUE
-
Uint8
20-06
Feedback 3 Source
[0] No function
All set-ups
TRUE
-
Uint8
20-07
Feedback 3 Conversion
[0] Linear
All set-ups
FALSE
-
Uint8
20-08
Feedback 3 Source Unit
ExpressionLimit
All set-ups
TRUE
-
Uint8
20-12
Reference/Feedback Unit
ExpressionLimit
All set-ups
TRUE
-
Uint8
20-2* Feedback/Setpoint
20-20
Feedback Function
[4] Maximum
All set-ups
TRUE
-
Uint8
20-21
Setpoint 1
0 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
20-22
Setpoint 2
0 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
20-23
Setpoint 3
0 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
20-6* Sensorless
20-60
Sensorless Unit
ExpressionLimit
All set-ups
TRUE
-
Uint8
20-69
Sensorless Information
0 N/A
All set-ups
TRUE
0
VisStr[25]
20-7* PID Autotuning
20-70
Closed Loop Type
[0] Auto
2 set-ups
TRUE
-
Uint8
20-71
PID Performance
[0] Normal
2 set-ups
TRUE
-
Uint8
20-72
PID Output Change
0.10 N/A
2 set-ups
TRUE
-2
Uint16
20-73
Minimum Feedback Level
-999999
ProcessCtrlUnit
2 set-ups
TRUE
-3
Int32
20-74
Maximum Feedback Level
999999
ProcessCtrlUnit
2 set-ups
TRUE
-3
Int32
20-79
PID Autotuning
[0] Disabled
All set-ups
TRUE
-
Uint8
20-8* PID Basic Settings
20-81
PID Normal/ Inverse Control
[0] Normal
All set-ups
TRUE
-
Uint8
20-82
PID Start Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
20-83
PID Start Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
20-84
On Reference Bandwidth
5%
All set-ups
TRUE
0
Uint8
20-9* PID Controller
20-91
PID Anti Windup
[1] On
All set-ups
TRUE
-
Uint8
20-93
PID Proportional Gain
2 N/A
All set-ups
TRUE
-2
Uint16
20-94
PID Integral Time
8 s
All set-ups
TRUE
-2
Uint32
20-95
PID Differentiation Time
0 s
All set-ups
TRUE
-2
Uint16
20-96
PID Diff. Gain Limit
5 N/A
All set-ups
TRUE
-1
Uint16
Parameter Lists
VLT
®
AQUA Drive FC 202
270
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
4