. The motor is
running and there are no warnings.
[8]
Run on
reference/no
warning
Motor runs at reference speed.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[10]
Alarm or
warning
An alarm or a warning activates the
output.
[11]
At torque limit The torque limit set in
parameter 4-16 Torque Limit Motor Mode
has been exceeded.
[12]
Out of current
range
The motor current is outside the range set
in
parameter 4-18 Current Limit
.
[13]
Below current,
low
Motor current is lower than the setting in
parameter 4-50 Warning Current Low
[14]
Above current,
high
Motor current is higher than the setting in
parameter 4-51 Warning Current High
.
[15]
Out of speed
range
Output speed is outside the ranges set in
parameter 4-52 Warning Speed Low
and
parameter 4-53 Warning Speed High
.
[16]
Below speed,
low
Output speed is lower than the setting in
parameter 4-52 Warning Speed Low
[17]
Above speed,
high
Output speed is higher than the setting in
parameter 4-53 Warning Speed High
.
[18]
Out of
feedback
range
Feedback is outside the ranges set in
parameter 4-56 Warning Feedback Low
and
parameter 4-57 Warning Feedback High
[19]
Below
feedback low
Feedback is below the limit set in
parameter 4-52 Warning Speed Low
[20]
Above
feedback high
The feedback is above the limit set in
parameter 4-56 Warning Feedback Low
.
[21]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor.
[25]
Reverse
Reversing. Logic 1 = relay activated, 24 V
DC when clockwise rotation of the motor.
Logic 0 = relay not activated, no signal,
when counterclockwise rotation of the
motor.
[26]
Bus OK
Active communication (no timeout) via the
serial communication port.
[27]
Torque limit
and stop
Used in performing a coast stop and in
torque limit condition. If the frequency
converter has received a stop signal and is
at the torque limit, the signal is logic 0.
[28]
Brake, no
warning
The brake is active and there are no
warnings.
[29]
Brake ready,
no fault
The brake is ready for operation and there
are no faults.
[30]
Brake fault
(IGBT)
The output is logic 1 when the brake IGBT
is short-circuited. Use this function to
protect the frequency converter if there is
a fault on the brake modules. Use the
output/relay to cut out the mains voltage
from the frequency converter.
[35]
External
Interlock
External interlock function has been
activated via 1 of the digital inputs.
[40]
Out of ref
range
[41]
Below
reference low
[42]
Above
reference high
[45]
Bus Ctrl
[46]
Bus Ctrl 1 if
timeout
[47]
Bus Ctrl 0 if
timeout
[55]
Pulse output
[60]
Comparator 0
See
parameter group 13-1* Comparators
. If
comparator 0 is evaluated as true, the
output goes high. Otherwise, it is low.
[61]
Comparator 1
See
parameter group 13-1* Comparators
. If
comparator 1 is evaluated as true, the
output goes high. Otherwise, it is low.
[62]
Comparator 2
See
parameter group 13-1* Comparators
. If
comparator 2 is evaluated as true, the
output goes high. Otherwise, it is low.
[63]
Comparator 3
See
parameter group 13-1* Comparators
. If
comparator 3 is evaluated as true, the
output goes high. Otherwise, it is low.
[64]
Comparator 4
See
parameter group 13-1* Comparators
. If
comparator 4 is evaluated as true, the
output goes high. Otherwise, it is low.
[65]
Comparator 5
See
parameter group 13-1* Comparators
. If
comparator 5 is evaluated as true, the
output goes high. Otherwise, it is low.
[70]
Logic Rule 0
See
parameter group 13-4* Logic Rules
. If
logic rule 0 is evaluated as true, the
output goes high. Otherwise, it is low.
[71]
Logic Rule 1
See
parameter group 13-4* Logic Rules
. If
logic rule 1 is evaluated as true, the
output goes high. Otherwise, it is low.
[72]
Logic Rule 2
See
parameter group 13-4* Logic Rules
. If
logic rule 2 is evaluated as true, the
output goes high. Otherwise, it is low.
[73]
Logic Rule 3
See
parameter group 13-4* Logic Rules
. If
logic rule 3 is evaluated as true, the
output goes high. Otherwise, it is low.
[74]
Logic Rule 4
See
parameter group 13-4* Logic Rules
. If
logic rule 4 is evaluated as true, the
output goes high. Otherwise, it is low.
[75]
Logic Rule 5
See
parameter group 13-4* Logic Rules
. If
logic rule 5 is evaluated as true, the
output goes high. Otherwise, it is low.
[80]
SL Digital
Output A
See
parameter 13-52 SL Controller Action
The output goes high whenever the smart
logic action
[38] Set digital out A high
is
Parameter Description
VLT
®
AQUA Drive FC 202
82
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
3
3