23-50 Energy Log Resolution
Option:
Function:
Week
, or
[2] Day of Month
. The counters
contain the logging data from the
programmed date/time for start
(
) and the
numbers of hours/days as programmed for
(
parameter 23-50 Energy Log Resolution
The logging starts on the date programmed
in
and continues
until 1 day/week/month has passed. The
counters contain data for 1 day, 1 week, or 5
weeks back in time, and up to the actual
time.
The logging starts at the date programmed
in
. In all cases,
the period split refers to operating hours
(time where frequency converter is powered
up).
[0]
Hour of Day
[1]
Day of Week
[2]
Day of
Month
[5]
*
Last 24
Hours
[6]
Last 7 Days
[7]
Last 5
Weeks
23-51 Period Start
Range:
Function:
Size
related
*
[ 0 -
0 ]
NOTICE
When mounting VLT
®
Analog I/O option
MCB 109, a battery back-up of the date
and time is included.
Set the date and time at which the energy log
starts updating the counters. First, data is
stored in counter [00] and start at the time/
date programmed in this parameter.
Date format depends on setting in
parameter 0-71 Date Format
and time format
on setting in
.
23-53 Energy Log
Array [31]
Range:
Function:
0
*
[0 -
4294967295 ]
NOTICE
All counters are automatically reset
when changing the setting in
parameter 23-50 Energy Log Resolution
.
At overflow, the update of the counters
stops at maximum value.
23-53 Energy Log
Array [31]
Range:
Function:
NOTICE
When mounting VLT
®
Analog I/O Option
MCB 109 option card, a battery back-up
of the date and time is included.
Array with several elements equal to the
number of counters ([00]-[xx] below parameter
number in display). Press [OK] and step
between elements with [
▲
] and [
▼
].
Array elements:
130BA280.11
23-5*
23-5*
23-5*
23-5*
23-5*
23-5*
23-5*
23-53 Ener gy met er
(00)
Ener gy met er
Ener gy met er
23-53 Ener gy met er
(01)
23-53 Ener gy met er
(02)
Ener gy met er
23-53 Ener gy met er
(03)
Ener gy met er
23-53 Ener gy met er
(04)
Ener gy met er
23-53 Ener gy met er
(05)
Ener gy met er
23-53 Ener gy met er
(06)
Ener gy met er
Illustration 3.76 Energy Log
Data from the latest period is stored in the
counter with the highest index.
At power-down, all counter values are stored
and resumed at next power-up.
23-54 Reset Energy Log
Option:
Function:
Select
[1] Do reset
to reset all values in the
energy log counters shown in
. After pressing OK,
the setting of the parameter value automatically
changes to
[0] Do not reset
.
[0]
*
Do not
reset
[1]
Do reset
Parameter Description
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
197
3
3