Example 2:
Variable = feedback, range = -200% to +200%.
Range needed for output = 0–100%.
Output signal 0 mA or 4 mA is needed at 0% (50% of
range). Set
parameter 6-51 Terminal 42 Output Min Scale
to
50%.
Output signal 20 mA is needed at 100% (75% of range).
Set
parameter 6-52 Terminal 42 Output Max Scale
to 75%.
0/4 mA
20 mA
50%
75%
100%
0%
0%
+100%
+200%
-200%
130BA856.10
Illustration 3.38 Example 2
Example 3:
Variable value = reference, range = minimum reference–
maximum reference
Range needed for output = minimum reference (0%)–
maximum reference (100%), 0–10 mA.
Output signal 0 mA or 4 mA is needed at minimum
reference. Set
parameter 6-51 Terminal 42 Output Min Scale
to 0%.
Output signal 10 mA is needed at maximum reference
(100% of range). Set
parameter 6-52 Terminal 42 Output
to 200%.
(20 mA/10 mA x 100%=200%).
20 mA
10 mA
0/4 mA
100%
200%
0%
Max ref
Max ref X 20/10
Min ref
130BA857.10
Illustration 3.39 Example 3
6-53 Terminal 42 Output Bus Control
Range:
Function:
0 %
*
[0 - 100 %] Holds the level of output 42 if controlled by
bus.
6-54 Terminal 42 Output Timeout Preset
Range:
Function:
0 %
*
[0 -
100 %]
Holds the preset level of output 42.
If a timeout function is selected in
parameter 6-50 Terminal 42 Output
, the output
is preset to this level if a fieldbus timeout
occurs.
6-55 Terminal 42 Output Filter
Option: Function:
The following readout parameters from selection in
parameter 6-50 Terminal 42 Output
have a filter
selected when
parameter 6-55 Terminal 42 Output Filter
is on:
Selection
0–20 mA
4–20 mA
Motor current (0–I
max
)
[103]
[133]
Torque limit (0–T
lim
)
[104]
[134]
Rated torque (0–T
nom
)
[105]
[135]
Power (0–P
nom
)
[106]
[136]
Speed (0–Speed
max
)
[107]
[137]
Table 3.19 Readout Parameters
[0]
*
Off Filter off.
[1]
On Filter on.
3.8.7 6-6* Analog Output X30/8
Analog outputs are current outputs: 0/4–20 mA. Common
terminal (terminal X30/8) is the same terminal and
electrical potential for analog common connection.
Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
Same options and functions as
.
Parameter Description
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
97
3
3