5-60 Terminal 27 Pulse Output Variable
Range:
Function:
[108] Torque
[109] Max Out Freq
[119] Torque % lim
5-62 Pulse Output Max Freq #27
Range:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
5000 Hz
*
[0 - 32000
Hz]
Set the maximum frequency for terminal
27 corresponding to the output variable
selected in
parameter 5-60 Terminal 27
Pulse Output Variable
.
5-63 Terminal 29 Pulse Output Variable
Option:
Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Select the variable for viewing on
terminal 29. Same options and
functions as
parameter group 5-6*
Pulse Output
.
[0]
*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[51]
MCO controlled
[100] Output freq. 0-100
[101] Reference Min-Max
[102] Fe-200%
[103] Motor cur. 0-Imax
[104] Torque 0-Tlim
[105] Torque 0-Tnom
[106] Power 0-Pnom
[107] Speed 0-HighLim
[108] -160%
[109] Out frq 0-Fmax
[113] Ext. Closed Loop 1
[114] Ext. Closed Loop 2
[115] Ext. Closed Loop 3
[116] Cascade Reference
5-65 Pulse Output Max Freq #29
Range:
Function:
5000 Hz
*
[0 - 32000
Hz]
Set the maximum frequency for terminal
29 corresponding to the output variable
set in
parameter 5-63 Terminal 29 Pulse
5-66 Terminal X30/6 Pulse Output Variable
Select the variable for readout on terminal X30/6.
This parameter is active when VLT
®
General Purpose I/O MCB 101
is installed in the frequency converter.
Same options and functions as
parameter group 5-6* Pulse
Outputs
.
Option:
Function:
[0]
*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[51]
MCO controlled
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[119]
Torque % lim
5-68 Pulse Output Max Freq #X30/6
Range:
Function:
5000.
Hz
*
[0 -
32000 Hz]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the maximum frequency on terminal
X30/6 referring to the output variable in
parameter 5-66 Terminal X30/6 Pulse Output
Variable
.
This parameter is active when VLT
®
General
Purpose I/O MCB 101 is installed in the
frequency converter.
5-80 AHF Cap Reconnect Delay
Range:
Function:
25 s
*
[1 - 120
s]
Delay time between 2 consecutive AHF
capacitor connections. The timer starts once
the AHF capacitor disconnects, and connects
back once delay expires and frequency
converters power above 20% and below 30%
of nominal power.
AHF capacitor connect output function for digital and
relay outputs
Functional description:
•
Connect capacitors at 20% nominal power.
•
Hysteresis
±
50% of 20% nominal power
(=minimum 10% and maximum 30% nominal
power).
Parameter Description
VLT
®
AQUA Drive FC 202
88
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02