10-23 COS Filter 4
Range:
Function:
0
*
[0 - 65535 ] Enter the value for COS filter 4 to set up the
filter mask for PCD 4. When operating in COS,
this function filters out bits in PCD 4 that
should not be sent if they change.
3.11.4 10-3* Parameter Access
Parameter group providing access to indexed parameters
and defining programming set-up.
10-30 Array Index
Range:
Function:
0
*
[0 - 255 ] View array parameters. This parameter is valid
only when a VLT
®
DeviceNet MCA 104 is installed.
10-31 Store Data Values
Option:
Function:
Parameter values changed via DeviceNet are not
automatically stored in non-volatile memory. Use
this parameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values are
retained at power-down.
[0]
*
Off
Deactivates the non-volatile storage function.
[1]
Store edit
setup
Stores all parameter values from the active set-
up in the non-volatile memory. The selection
returns to
[0] Off
when all values have been
stored.
[2]
Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
[0]
Off
when all parameter values have been stored.
10-32 Devicenet Revision
Range:
Function:
Size related
*
[0 - 65535 ] View the DeviceNet revision number.
This parameter is used for EDS file
creation.
10-33 Store Always
Option: Function:
[0]
*
Off Deactivates non-volatile storage of data.
[1]
On Stores parameter data received via VLT
®
DeviceNet
MCA 104 in EEPROM non-volatile memory as default.
10-34 DeviceNet Product Code
Range:
Function:
0 N/A
*
[0 - 65535 N/A]
10-39 Devicenet F Parameters
Array [1000].
No LCP access.
Range:
Function:
0
*
[0 - 0 ] This parameter is used to configure the frequency
converter via VLT
®
DeviceNet MCA 104 and to
build the EDS file.
Parameter Description
VLT
®
AQUA Drive FC 202
112
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
3
3