Start the motor at nominal speed. If the application does
not run well, check the VVC
+
SynRM settings.
contains recommendations for various applications.
Application
Settings
Low-inertia applications
I
Load
/I
Motor
<5
Increase
by factor 5–10.
Reduce
Reduce
(<100%).
Low-inertia applications
50>I
Load
/I
Motor
>5
Keep the default values.
High-inertia applications
I
Load
/I
Motor
>50
Increase
parameter 1-15 Low Speed Filter
Time Const.
, and
parameter 1-16 High
Speed Filter Time Const.
High load at low speed
<30% (rated speed)
Increase
Increase
to adjust the starting
torque. 100% current provides
nominal torque as starting torque.
Working at a current level higher
than 100% for a prolonged time can
cause the motor to overheat.
Table 3.5 Recommendations for Various Applications
If the motor starts oscillating at a certain speed, increase
. Increase the value in small
steps. Depending on the motor, this parameter can be set
to 10–100% higher than the default value.
3.3.6 1-1* VVC
+
PM/SynRM
The default control parameters for VVC
+
PMSM control core
are optimized for applications and inertia load in range of
50>Jl/Jm>5. Jl is load inertia from the application and Jm
is machine inertia.
For low-inertia applications (Jl/Jm<5), increase
parameter 1-17 Voltage filter time const.
with a factor of 5–
10 and sometimes
to
improve performance and stability.
For high-inertia applications (Jl/Jm>50) increase
parameter 1-15 Low Speed Filter Time Const.
parameter 1-16 High Speed Filter Time Const.
, and
to improve performance and
stability.
For high load at low speed (<30% of rated speed), increase
parameter 1-17 Voltage filter time const.
due to non-linearity
in the inverter at low speed.
1-11 Motor Model
Option:
Function:
Automatically sets the factory values for the
selected motor. If the default value
Std.
Asynchron
is used, determine settings
manually according to the selection
parameter 1-10 Motor Construction
.
[1]
Std.
Asynchron
Default motor model when
[0] Asynchron
is
selected in
parameter 1-10 Motor Construction
.
[2]
Std. PM, non
salient
Selectable when
[1] PM, non-salient SPM
is
selected in
parameter 1-10 Motor Construction
.
[10] Danfoss OGD
LA10
Selectable when
[1] PM, non-salient SPM
is
selected in
parameter 1-10 Motor Construction
.
Only available for T4, T5 in 1.5–3 kW. Settings
are loaded automatically for this specific
motor.
[11] Danfoss OGD
V210
Selectable when
[1] PM, non-salient SPM
is
selected in
parameter 1-10 Motor Construction
.
Only available for T4, T5 in 0.75–3 kW.
Settings are loaded automatically for this
specific motor.
1-14 Damping Gain
Range:
Function:
Size
related
*
[0 -
250 %
]
The parameter stabilizes the PM motor so it
runs smoothly and with stability. The value of
damping gain controls the dynamic
performance of the PM motor. Low damping
gain results in high dynamic performance and
a high value results in a low dynamic
performance. If the damping gain is too high
or low, the control becomes unstable. The
resulting dynamic performance is related to
the machine data and load type.
1-15 Low Speed Filter Time Const.
Range:
Function:
Size
related
*
[0.01 -
20 s]
High-pass filter damping time constant
determines the response time to load
steps. Obtain quick control through a
short damping time constant. However,
if this value is too low, the control
becomes unstable. This time constant is
used below 10% rated speed.
1-16 High Speed Filter Time Const.
Range:
Function:
Size
related
*
[0.01 -
20 s]
High-pass filter damping time constant
determines the response time to load
steps. Obtain quick control through a
short damping time constant. However,
if this value is too low, the control
becomes unstable. This time constant is
used above 10% rated speed.
Parameter Description
VLT
®
AQUA Drive FC 202
46
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02