13-20 SL Controller Timer
Array [8]
Range:
Function:
Size
related
*
[ 0 -
0 ]
Enter the value to define the duration of
the false output from the programmed
timer. A timer is only false if it is started
by an action (for example
[29] Start timer
1
) and until the given timer value has
elapsed.
3.12.5 13-4* Logic Rules
Combine up to 3 boolean inputs (true/false inputs) from
timers, comparators, digital inputs, status bits, and events
using the logical operators AND, OR, and NOT. Select
boolean inputs for the calculation in
parameter 13-42 Logic Rule Boolean 2
, and
parameter 13-44 Logic Rule Boolean 3
. Define the operators
used to logically combine the selected inputs in
parameter 13-41 Logic Rule Operator 1
and
parameter 13-43 Logic Rule Operator 2
. . .
. . .
. . .
. . .
Par. 13-43
Logic Rule Operator 2
Par. 13-41
Logic Rule Operator 1
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-44
Logic Rule Boolean 3
130BB673.10
Illustration 3.44 Logic Rules
Priority of calculation
The results of
parameter 13-40 Logic Rule Boolean 1
parameter 13-41 Logic Rule Operator 1
, and
parameter 13-42 Logic Rule Boolean 2
are calculated first.
The outcome (true/false) of this calculation is combined
with the settings of
parameter 13-43 Logic Rule Operator 2
and
parameter 13-44 Logic Rule Boolean 3
, yielding the final
result (true/false) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[0]
False
Enters the fixed value of false in the
logic rule.
[1]
True
Enters the fixed value of true in the
logic rule.
[2]
Running
See
parameter group 5-3* Digital
Outputs
for further description.
[3]
In range
See
parameter group 5-3* Digital
Outputs
for further description.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[4]
On reference
See
parameter group 5-3* Digital
Outputs
for further description.
[5]
Torque limit
See
parameter group 5-3* Digital
Outputs
for further description.
[6]
Current Limit
See
parameter group 5-3* Digital
Outputs
for further description.
[7]
Out of current
range
See
parameter group 5-3* Digital
Outputs
for further description.
[8]
Below I low
See
parameter group 5-3* Digital
Outputs
for further description.
[9]
Above I high
See
parameter group 5-3* Digital
Outputs
for further description.
[10]
Out of speed
range
[11]
Below speed low
See
parameter group 5-3* Digital
Outputs
for further description.
[12]
Above speed high See
parameter group 5-3* Digital
Outputs
for further description.
[13]
Out of feedb.
range
See
parameter group 5-3* Digital
Outputs
for further description.
[14]
Below feedb. low
See
parameter group 5-3* Digital
Outputs
for further description.
[15]
Above feedb. high See
parameter group 5-3* Digital
Outputs
for further description.
[16]
Thermal warning
See
parameter group 5-3* Digital
Outputs
for further description.
[17]
Mains out of
range
See
parameter group 5-3* Digital
Outputs
for further description.
[18]
Reversing
See
parameter group 5-3* Digital
Outputs
for further description.
[19]
Warning
See
parameter group 5-3* Digital
Outputs
for further description.
[20]
Alarm (trip)
See
parameter group 5-3* Digital
Outputs
for further description.
[21]
Alarm (trip lock)
See
parameter group 5-3* Digital
Outputs
for further description.
[22]
Comparator 0
Use the result of comparator 0 in the
logic rule.
[23]
Comparator 1
Use the result of comparator 1 in the
logic rule.
[24]
Comparator 2
Use the result of comparator 2 in the
logic rule.
[25]
Comparator 3
Use the result of comparator 3 in the
logic rule.
Parameter Description
VLT
®
AQUA Drive FC 202
122
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
3
3