SiE12-411
Others
Others
257
1.2
Jumper Settings
1.2.1 When Two Units are Installed in One Room
"
How to set the different addresses.
"
When two indoor units are installed in one room, the two wireless remote controllers can be
set for different addresses.
PCB in the indoor unit
"
Remove the front panel.
"
Remove the sensor parts cover (2-screws), then remove the electric parts box (1-screw).
"
Slide the metallic cover to remove it. (4-claws on the electric parts box.)
"
Cut the jumper JA on PCB.
Wireless remote controller (in case of wall mounted type)
"
Cut the jumper J4.
1.2.2 Jumper Setting
Addre
ss
J4
CUT
EXI
S
T
1
2
ADDRE
SS
J4
CUT
EXI
S
T
1
2
JA
JB
JC
Met
a
llic cover
PCB
Cl
a
w
s
(4 point
s
)
(R25
8
7)
Infr
a
red
remote
control
ADDRE
SS
: JA
Electric
p
a
rt
s
b
ox
S
en
s
or
p
a
rt
s
cover
Jumper
(On indoor PCB)
Function
When connected
(factory set)
When cut
JC
Power failure
recovery function
Auto start
Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
JB
Fan speed setting
when compressor is
OFF on thermostat.
Fan speed setting ;
Remote controller
setting
Fan rpm is set to “0”
<Fan stop>
Summary of Contents for Super Multi NX C-Series
Page 6: ...SiE12 411 Table of Contents v Index i Drawings Flow Charts v...
Page 7: ...SiE12 411 vi Table of Contents...
Page 67: ...Specifications SiE12 411 56 Specifications...
Page 171: ...Instruction SiE12 411 160 System Configuration...
Page 225: ...Check SiE12 411 214 Service Diagnosis...
Page 295: ...SiE12 411 iv Index...