![background image](http://html1.mh-extra.com/html/daikin/super-multi-nx-c-series/super-multi-nx-c-series_service-manual_3794977259.webp)
Outdoor Unit (50 / 52 / 58 / 68 / 75 Class)
SiE12-411
248
Removal Procedure
2.4
Removal of Fan Motor
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
"
Remove the fan motor
lead wire connector.
"
For reassembling, align
mark of propeller fan with
D-cut section of motor shaft.
"
Mount the propeller fan while
positioning
!
mark to the
top.
1
Remove the propeller
fan by removing the
washer-fitted nut.
2
Remove the fan motor.
Remove 1 screw of the
fan motor mount.
"
When reassembling, fix the
lead wire to avoid contact
with the propeller fan.
3
Disconnect the lead
wire by releasing the 2
clamps fixing the wire.
Remove 4 screws of
the fan motor.
W
as
her-fitted n
u
t
(B
a
ck
s
ide)