SiE12-411
Troubleshooting
Service Diagnosis
175
5.6
Thermistor or Related Abnormality (Indoor Unit)
Remote
Controller
Display
C4, C9
Method of
Malfunction
Detection
The temperatures detected by the thermistors are used to determine thermistor errors.
Malfunction
Decision
Conditions
When the thermistor input is more than 4.96 V or less than 0.04 V during compressor
operation
∗
.
∗
(reference)
When above about 212°C (less than 120 ohms) or below about -50°C (more than 1,860 kohms).
Note:
The values vary slightly in some models.
Supposed
Causes
"
Faulty connector connection
"
Faulty thermistor
"
Faulty PCB
Troubleshooting
Check No.6
Refer to P.207
C4
: Heat exchanger temperature thermistor
C9
: Room temperature thermistor
Check the connector connection.
YE
S
Correct the connection.
Repl
a
ce the thermi
s
tor.
(Repl
a
ce the indoor
u
nit PCB.)
Repl
a
ce the indoor
u
nit PCB.
I
s
it norm
a
l?
I
s
it norm
a
l?
(R140
3
)
NO
Check No. 6
Thermi
s
tor re
s
i
s
t
a
nce check
YE
S
NO
Caution
Be
su
re to t
u
rn off power
s
witch
b
efore connect or di
s
connect connector,
or p
a
rt
s
d
a
m
a
ge m
a
y
b
e occ
u
rred.
Summary of Contents for Super Multi NX C-Series
Page 6: ...SiE12 411 Table of Contents v Index i Drawings Flow Charts v...
Page 7: ...SiE12 411 vi Table of Contents...
Page 67: ...Specifications SiE12 411 56 Specifications...
Page 171: ...Instruction SiE12 411 160 System Configuration...
Page 225: ...Check SiE12 411 214 Service Diagnosis...
Page 295: ...SiE12 411 iv Index...