SiUS39-602
Specifications
Specifications
9
Notes:
★
1 Indoor temp. : 80°FDB or 67°FWB / outdoor temp. : 95°FDB / Equivalent piping length : 25 ft, level
difference: 0.
★
2 Indoor temp. : 70°FDB / outdoor temp. : 47°FDB or 43°FWB / Equivalent piping length : 25 ft, level
difference: 0.
★
3 BHFP26M90V is necessary for the connection.
Concerning about the piping connection for each outdoor unit to the main line as shown above, use REFNET.
Model Name (Combination Unit)
REYQ168MTJU
Model Name (Independent Unit)
REYREYQ96MTJU
★
1 Cooling Capacity
Btu / h
168,000
★
2 Heating Capacity
Btu / h
189,000
Casing Color
Ivory White (5Y7.5/1)
Dimensions: (H×W×D)
in
(64 × 48-7/8 × 30-1/8) + (64 × 48-7/8 × 30-1/8)
Heat Exchanger
Cross Fin Coil
Comp.
Type
Hermetically Sealed Scroll Type
Piston Displacement
m³/h
(13.72+10.47) × 2
Number of Revolutions
r.p.m
(6480, 2900) × 2
Motor Output × Number
of Units
kW
(2.7+4.5) × 2
Starting Method
Direct on line
Fan
Type
Propeller Fan
Motor Output
kW
0.75 × 2
Air Flow Rate
cfm
7,400 + 7,400
Drive
Direct Drive
Connecting
Pipes
Liquid Pipe
★
3
in
5/8 in C1220T (Brazing Connection) — Main line —
Suction Gas Pipe
★
3
in
1-1/8 in C1220T (Brazing Connection) — Main line —
Discharge Gas Pipe
★
3
in
7/8 in C1220T (Brazing Connection) — Main line —
Oil Equalizing Pipe
in
1/4 in C1220T (Flare Connection)
Machine Weight (Mass)
Lbs
666+666
Safety Devices
High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector, Fusible Plugs,
Ground fault circuit interrupter
Defrost Method
Deicer
Capacity Control
%
7~100
Refrigerant
Refrigerant Name
R-410A Series
Charge Lbs
27.3+27.3
Control
Electronic Expansion Valve
Refrigerator
Oil
Synthetic (ether) oil
Charge Volume
L
(1.9+1.6) + (1.9+1.6)
Standard Accessories
Installation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
4D053305
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...