![background image](http://html1.mh-extra.com/html/daikin/reyq72/reyq72_serveice-manual_4175337018.webp)
SiUS39-602
Specifications
Specifications
7
Notes:
★
1 Indoor temp. : 80°FDB or 67°FWB / outdoor temp. : 95°FDB / Equivalent piping length : 25 ft, level
difference: 0.
★
2 Indoor temp. : 70°FDB / outdoor temp. : 47°FDB or 43°FWB / Equivalent piping length : 25 ft, level
difference: 0.
★
3 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Model Name
REYQ96MTJU
★
1 Cooling Capacity
Btu / h
96,000
★
2 Heating Capacity
Btu / h
108,000
Casing Color
Ivory White (5Y7.5/1)
Dimensions: (H×W×D)
in
64 × 48-7/8 × 30-1/8
Heat Exchanger
Cross Fin Coil
Comp.
Type
Hermetically Sealed Scroll Type
Piston Displacement
m³/h
13.72+10.47
Number of Revolutions
r.p.m
6480, 2900
Motor Output × Number
of Units
kW
(2.7+4.5) × 1
Starting Method
Direct on line
Fan
Type
Propeller Fan
Motor Output
kW
0.75 × 1
Air Flow Rate
cfm
7,400
Drive
Direct Drive
Connecting
Pipes
Liquid Pipe
in
3/8 in C1220T (Flare Connection)
Gas Pipe
in
7/8 in C1220T (Brazing Connection)
Discharge Gas Pipe
in
3/4 in C1220T (Brazing Connection)
Machine Weight (Mass)
Lbs
666
★
3 Sound Level (Reference Value)
dBA
60
Safety Devices
High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector, Fusible Plugs
Defrost Method
Deicer
Capacity Control
%
14~100
Refrigerant
Refrigerant Name
R-410A Series
Charge Lbs
27.3
Control
Electronic Expansion Valve
Refrigerator
Oil
Synthetic (ether) oil
Charge Volume
L
1.9+1.6
Standard Accessories
Installation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
4D045327A
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 602 iv Index...