SiUS39-602
Basic Control
Function
47
2.5
Heat Exchange Mode in Heating Operation or
Simultaneous Cooling / Heating Operation
In heating or simultaneous cooling / heating operation, a target condensing and evaporating
temperature can be secured by switching the air heat exchanger of the outdoor unit (main, sub)
into evaporator or condenser with load.
Step A1
Master unit
Slave unit 1
Slave unit 2
Main heat exchanger Sub heat exchanger
Condenser
Condenser
Not used
Not used
Condenser
Condenser
Master unit
Slave unit 1
Slave unit 2
Main heat exchanger Sub heat exchanger
Evaporator
Condenser
Evaporator
Not used
Not used
Not used
Master unit
Slave unit 1
Slave unit 2
Main heat exchanger Sub heat exchanger
Evaporator
Condenser
Evaporator
Evaporator
Not used
Not used
Step A2
Step A3
Step B1
Step B2
Master unit
Slave unit 1
Slave unit 2
Main heat exchanger Sub heat exchanger
Not used
Condenser
Not used
Not used
Condenser
Condenser
Master unit
Slave unit 1
Slave unit 2
Main heat exchanger Sub heat exchanger
Not used
Condenser
Not used
Not used
Condenser
Not used
Master unit
Slave unit 1
Slave unit 2
Main heat exchanger Sub heat exchanger
Evaporator
Condenser
Not used
Not used
Not used
Not used
Step B3
GR > 900
GR < –250
GR > 250
GR < –250
GR > 250
GR < –250
GR > 250
GR < –250
GR > 250
GR < –250
Master unit
Slave unit 1
Slave unit 2
Main heat exchanger Sub heat exchanger
Evaporator
Evaporator
Evaporator
Not used
Evaporator
Not used
Master unit
Slave unit 1
Slave unit 2
Main heat exchanger Sub heat exchanger
Evaporator
Evaporator
Evaporator
Evaporator
Evaporator
Evaporator
Step C1
Step C2
Master unit
Slave unit 1
Slave unit 2
Main heat exchanger Sub heat exchanger
Evaporator
Evaporator
Not used
Not used
Not used
Not used
Step C3
GR > 250
GR < – 250
GR > 250
GR < –250
GR > 900
GR > –400
*
• The GR is a numerical value representing the current balancing
conditions, which is computed in accordance with the target
condensing temperature, target evaporating temperature, current
condensing temperature, and current evaporating temperature.
• If there are no steps to receive transition when one or two outdoor
units are installed, the steps will be skipped.
* Not used: The meaning of "not used" is
that the refrigerant is not flowing to
heat exchanger by closing EX valves
of changing over the 4 way valves.
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 602 iv Index...