Basic Control
SiUS39-602
42
Function
Compressor Operating Priority
INV:
Inverter compressor
STD1: Standard compressor 1
Each compressor operates in the following order of priority.
REYQ72M
INV
STD1
No. 1 No. 2
REYQ96M
INV
STD1
No. 1 No. 2
REYQ72M
STEP
INV
STD1
1
52Hz
OFF
2
57Hz
OFF
3
62Hz
OFF
4
68Hz
OFF
5
74Hz
OFF
6
81Hz
OFF
7
88Hz
OFF
8
96Hz
OFF
9
104Hz
OFF
10
110Hz
OFF
11
116Hz
OFF
12
124Hz
OFF
13
133Hz
OFF
14
143Hz
OFF
15
158Hz
OFF
16
165Hz
OFF
17
177Hz
OFF
18
189Hz
OFF
19
202Hz
OFF
20
210Hz
OFF
21
52Hz
ON
22
74Hz
ON
23
96Hz
ON
24
116Hz
ON
25
133Hz
ON
26
158Hz
ON
27
177Hz
ON
28
202Hz
ON
29
210Hz
ON
∗
•
Compressors are operated in the order of descending priorities.
•
Compressors may operate in a pattern other than those listed in above tables subject to the operating conditions.
•
“Master unit”, and “slave unit” in this section are the names for control, and they will be transferred according to the
priority of rotation system.
REYQ96M
STEP
INV
STD1
1
52Hz
OFF
2
57Hz
OFF
3
62Hz
OFF
4
68Hz
OFF
5
74Hz
OFF
6
81Hz
OFF
7
88Hz
OFF
8
96Hz
OFF
9
104Hz
OFF
10
110Hz
OFF
11
116Hz
OFF
12
124Hz
OFF
13
133Hz
OFF
14
143Hz
OFF
15
158Hz
OFF
16
165Hz
OFF
17
177Hz
OFF
18
189Hz
OFF
19
202Hz
OFF
20
210Hz
OFF
21
52Hz
ON
22
74Hz
ON
23
96Hz
ON
24
116Hz
ON
25
133Hz
ON
26
158Hz
ON
27
177Hz
ON
28
202Hz
ON
29
210Hz
ON
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 602 iv Index...