Troubleshooting by Indication on the Remote Controller
SiUS39-602
146
Troubleshooting
2.17
“
E6
”
Compressor Motor Overcurrent/Lock (STD Compressor)
Remote
Controller
Display
E6
Applicable
Models
REYQ72M, 96M
Method of
Malfunction
Detection
Detects the overcurrent with current sensor (CT).
Malfunction
Decision
Conditions
Malfunction is decided when the detected current value exceeds the below mentioned value for
2 seconds.
200 V unit : 34.0 A
Supposed
Causes
Closed stop value
Obstacles at the discharge port
Improper power voltage
Faulty magnetic switch
Faulty compressor
Faulty current sensor
Troubleshooting
Note:
Abnormal case
The current sensor value is 0 during STD compressor operation.
The current sensor value is more than 15.0A during STD compressor operation.
Is the stop valve open?
NO
Obstacle
exists around the air
discharge port.
YES
Is the power
supply voltage
normal?
NO
NO
NO
YES
NO
Is the
magnetic switch
(K2M, K3M)
normal?
Is
above wiring
correct?
NO
Is
current sensor
correct?
Check the wiring from power supply ~ current sensor (A5P, A6P) ~
MgS (K2M, K3M) ~ compressor
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Open the stop valve.
Remove the obstacle.
Correct the power voltage.
Replace the magnetic
switch.
Correct wiring.
Replace the corresponding
current sensor
(A5P or A6P).
Replace compressor.
(V3051)
YES
YES
YES
YES
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 602 iv Index...