Troubleshooting by Indication on the Remote Controller
SiUS39-602
148
Troubleshooting
Troubleshooting
Refer check 8, 9 and 12 to P.212
~
213.
Check No. 12
Check on pulse input of
position signal of fan inverter
PCB
YES
Check No. 8
Check on connector of fan
motor (Power supply cable)
YES
Is the LED
(HAP) on fan inverter
PCB blinking?
NO
Check No. 9
Check on connector of fan
motor (Signal wire)
YES
Are the
resistance values
between phases of
U, V, W balanced?
Is there any short
circuiting between
phases of
U, V, W?
NO
Is the
resistance value
between Vcc and UVW,
and GND and UVW
balanced?
NO
Replace the fan inverter
PCB.
Replace the fan motor of
outdoor unit.
Replace the fan motor of
outdoor unit.
Replace the fan inverter
PCB.
(V3077)
1A
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 602 iv Index...