SiUS39-602
Field Setting
Test Operation
91
3.2
Field Setting from Outdoor Unit
3.2.1 Field Setting from Outdoor Unit
Setting by dip switches
The following field settings are made by dip switches on PC board.
Dipswitch
Setting item
Description
No.
Setting
DS1-1
ON
Not used
Do not change the factory settings.
OFF (Factory set)
DS1-2
~DS1-4
ON
Not used
Do not change the factory settings.
OFF (Factory set)
DS2-1
~4
ON
Not used
Do not change the factory settings.
OFF (Factory set)
DS3-1,
2
ON
Not used
Do not change the factory settings.
OFF (Factory set)
Caution
DIP switch Setting after changing the main P.C.Board(A1P) to spare parts P.C.B.
When you change the main P.C.Board(A1P) to spare parts P.C.B., please carry out the following
setting.
DIP Switch Detail
DS No.
Item
Contents
DS1-1
—
—
DS1-2
Power supply
setting
ON
3 phase 200 Volt area
OFF 3 phase 400 Volt area
DS1-3
—
—
DS1-4
Refrigerant
classification
(Do not set)
DS2-1
DS2-2
Capacity setting
DS2-3
DS2-4
1 2 3 4
1 2 3 4
DS1
DS2
ON
OFF
ON
OFF
R-410A
DS1-4
OFF
DS2-1
ON
72, 96
DS2-2
OFF
DS2-3
OFF
DS2-4
ON
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 602 iv Index...