Specifications
SiUS39-602
16
Specifications
Ceiling Mounted Built-in Type
Notes:
★
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25ft (Horizontal)
★
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
★
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
means
"High static pressure – Standard".
★
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model
FXSQ30MVJU
FXSQ36MVJU
FXSQ48MVJU
★
1 Cooling Capacity
Btu/h
30,000
36,000
48,000
★
2 Heating Capacity
Btu/h
34,000
40,000
54,000
Casing / Color
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Dimensions: (H×W×D)
in
11-7/8
×
55-1/8
×
31-1/2
11-7/8
×
55-1/8
×
31-1/2
11-7/8
×
55-1/8
×
31-1/2
Coil (Cross
Fin Coil)
Rows × Stages × FPI
3
×
14
×
14
3
×
14
×
14
3
×
14
×
14
Face Area
ft²
3.64
3.64
3.64
Fan
Model
3D18H2A
3D18H2A
3D18H2A
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output
HP
0.30
0.30
0.30
Air Flow Rate (H/L)
cfm
950/720
990/740
1,300/950
External Static Pressure
★
4
in. Aq
0.57-0.39
0.57-0.35
0.34-0.10
Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Glass Fiber
Glass Fiber
Glass Fiber
Air Filter
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Piping
Connections
Liquid Pipes
in
φ
3/8 (Flare Connection)
φ
3/8 (Flare Connection)
φ
3/8 (Flare Connection)
Gas Pipes
in
φ
5/8 (Flare Connection)
φ
5/8 (Flare Connection)
φ
5/8 (Flare Connection)
Drain Pipe
in
VP25
(External Dia. 1-1/4 Internal Dia. 1)
VP25
(External Dia. 1-1/4 Internal Dia. 1)
VP25
(External Dia. 1-1/4 Internal Dia. 1)
Machine Weight (Mass)
Lbs
119
119
122
★
5 Sound Level (H/L)
dBA
45/39
45/39
48/43
Safety Devices
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Connectable outdoor unit
R-410A Series
R-410A Series
R-410A Series
Decoration
Panel
(Option)
Model
BYBS125DJW1
BYBS125DJW1
BYBS125DJW1
Panel Color
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
Dimensions: (H×W×D)
in
2-1/8
×
59
×
19-5/8
2-1/8
×
59
×
19-5/8
2-1/8
×
59
×
19-5/8
Weight
Lbs
14
14
14
Standard Accessories
Operation Manual, Installation
Manual, Paper Pattern for
Installation, Drain Hose, Clamp
Metal, Insulation for Fitting, Sealing
Pads, Clamps, Screws, Washers.
Operation Manual, Installation
Manual, Paper Pattern for
Installation, Drain Hose, Clamp
Metal, Insulation for Fitting, Sealing
Pads, Clamps, Screws, Washers.
Operation Manual, Installation
Manual, Paper Pattern for
Installation, Drain Hose, Clamp
Metal, Insulation for Fitting, Sealing
Pads, Clamps, Screws, Washers.
Drawing No.
C:3D042684
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 602 iv Index...