![background image](http://html1.mh-extra.com/html/daikin/reyq72/reyq72_serveice-manual_4175337029.webp)
Specifications
SiUS39-602
18
Specifications
Ceiling Suspended Type
Notes:
★
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping: 25ft (Horizontal)
★
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
★
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Model
FXHQ12MVJU
FXHQ24MVJU
FXHQ36MVJU
★
1 Cooling Capacity
Btu/h
12,000
24,000
36,000
★
2 Heating Capacity
Btu/h
13,500
27,000
40,000
Casing Color
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
Dimensions: (H×W×D)
in
7-11/16×37-13/16×26-3/4
7-11/16×55-1/8×26-3/4
7-11/16×62-5/8×26-3/4
Coil (Cross
Fin Coil)
Rows × Stages × FPI
2×12×15
3×12×15
2×12×15+2×10×15
Face Area
ft²
1.96
3.15
3.66+2.95
Fan
Model
3D12K1AA1
3D12K2AA1
3D12K2AA1
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output
W
62
130
130
Air Flow Rate (H/L)
CFM
410/340
710/600
830/670
Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Glass Wool
Glass Wool
Glass Wool
Air Filter
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Piping
Connections
Liquid Pipes
in
φ
1/4 (Flare Connection)
φ
3/8 (Flare Connection)
φ
3/8 (Flare Connection)
Gas Pipes
in
φ
1/2 (Flare Connection)
φ
5/8 (Flare Connection)
φ
5/8 (Flare Connection)
Drain Pipe
in
VP20
(External Dia. 1, Internal Dia. 3/4)
VP20
(External Dia. 1, Internal Dia. 3/4)
VP20
(External Dia. 1, Internal Dia. 3/4)
Machine Weight (Mass)
Lbs
55
80
90
★
4 Sound Level (H)
dBA
42
44
46
Safety Devices
Fuse
Thermal Protector for Fan Motor
Fuse
Thermal Protector for Fan Motor
Fuse
Thermal Protector for Fan Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Connectable Outdoor Unit
R-410A Series
R-410A Series
R-410A Series
Standard Accessories
Operation Manual, Installation
Manual, Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation
for Fitting, Clamps, Washers.
Operation Manual, Installation
Manual, Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation
for Fitting, Clamps, Washers.
Operation Manual, Installation
Manual, Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation
for Fitting, Clamps, Washers.
Drawing No.
4D049326
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 602 iv Index...