SiUS39-602
Field Setting
Test Operation
95
8
: ON
7
: OFF
9
: Blink
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set
0
EMG (emergency
operation)
INV compressor
operation inhibited.
8
7
7
7
7
7
7
Normal operation
8777778
∗
Emergency operation
8777787
1
—
2
Low noise/demand
address
8
7
7
7
7
8
7
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
31
8788888
5
Indoor forced fan H
8
7
7
7
8
7
8
Normal operation
8777778
∗
Indoor forced fan H
8777787
6
Indoor forced
operation
8
7
7
7
8
8
7
Normal operation
8777778
∗
Indoor forced operation
8777787
8
Te setting
8
7
7
8
7
7
7
High
8777877
Normal (factory setting)
8777787
∗
Low
8777778
9
Tc setting
8
7
7
8
7
7
8
High
8777877
Normal (factory setting)
8777787
∗
Low
8777778
10 Defrost setting
8
7
7
8
7
8
7
Quick defrost
8777877
Normal (factory setting)
8777787
∗
Slow defrost
8777778
11
Sequential operation
setting
8
7
7
8
7
8
8
OFF
8777778
ON
8777787
∗
12
External low noise/
demand setting
8
7
7
8
8
7
7
External low noise/demand:
NO
8777778
∗
External low noise/demand:
YES
8777787
13 Airnet address
8
7
7
8
8
7
8
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
63
8788888
18
High static pressure
setting
8
7
8
7
7
8
7
High static pressure setting:
OFF
8777778
∗
High static pressure setting:
ON
8777787
19
Emergency
operation
(STD compressor is
inhibited to operate.)
8
7
8
7
7
8
8
OFF
8777777
∗
STD 1, 2 operation: Inhibited
8777778
STD 2 operation: Inhibited
8777787
20
Additional refrigerant
charge operation
setting
8
7
8
7
8
7
7
Refrigerant charging: OFF
/vacuuming
8777778
∗
Refrigerant charging: ON
/vacuuming
8777787
21
Refrigerant recovery
/vacuuming mode
setting
8
7
8
7
8
7
8
Refrigerant recovery: OFF
8777778
∗
Refrigerant recovery: ON
8777787
22
Night-time low noise
setting
8
7
8
7
8
8
7
OFF
8777777
∗
Level 1 (outdoor fan with 6 step or lower)
8777778
Level 2 (outdoor fan with 5 step or lower)
8777787
Level 3 (outdoor fan with 4 step or lower)
8777788
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 602 iv Index...