Troubleshooting by Indication on the Remote Controller
SiUS39-602
130
Troubleshooting
Troubleshooting
(V2778)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Replace float switch.
Modify the float switch's
connection and turn on again.
Connect the drain pump and
turn on again.
Check the drain piping for
clogging or upward slope, etc.
Replace indoor unit PC board.
Replace the drain pump or
check for dirt, etc.
Connect either a short circuit
connector or float switch and
turn on again.
YES
YES
YES
YES
YES
Defect of indoor unit PC board.
Loose connection of connector.
NO
NO
NO
YES
YES
NO
NO
YES
NO
YES
NO
NO
The float
switch is connected to
X8A of the indoor unit
PC board.
NO
The drain
pump works when
the power supply is reset
for the indoor
unit.
The drain
pump is connected
to X25A or terminals Y1
and Y2 of the
indoorunit PC
board.
The voltage
of terminals Y1
and Y2 or X25A is
208~230 V (within
5minutes of resetting
the power
supply).
Water builds up
in the drain pan.
The float
switch contact is
forming a short circuit
(continuity check
with X8A or X15A
disconnected)
A short
circuit connector is
connected to
X8A.
Provide 208~230V power
supply.
YES
NO
Is power supply
208~230V provided?
Becomes
normal when X8A of
the indoor unit PC board
is short circuited
The float switch
functions normally.
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 602 iv Index...