Field Setting
Test Operation
83
3.1.5 Applicable Range of Field Setting
∗
1. Static pressure selection
3.1.6
Detailed Explanation of Setting Modes
Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
Ultra-Long-Life Filter Sign Setting
When a Ultra-long-life filter is installed, the filter sign timer setting must be changed.
Setting Table
Ceiling
mounted
cassette
type
Slim Ceiling
mounted
duct type
Ceiling
mounted
built-in type
Ceiling
mounted
duct type
Ceiling
suspended
type
Wall
mounted
type
Floor
standing
type
Concealed
Floor
standing
type
Multi flow
FXFQ
FXDQ
FXSQ
FXMQ
FXHQ
FXAQ
FXLQ
FXNQ
Filter sign
{
{
{
{
{
{
{
{
Ultra long life filter sign
{
—
—
—
—
—
—
—
Remote controller thermostat
sensor
{
{
{
{
{
{
{
{
Set fan speed when thermostat
OFF
{
{
{
{
{
{
{
{
Air flow adjustment Ceiling
height
{
—
—
—
{
{
—
—
Air flow direction
{
—
—
—
—
—
—
—
Air flow direction adjustment
(Down flow operation)
—
—
—
—
—
—
—
—
Air flow direction adjustment
range
{
{
∗
1
—
—
—
—
—
—
Filter Specs.
Setting
Standard
Long Life
Ultra Long Life Filter
Contamination Light
200 hrs.
2,500 hrs.
10,000 hrs.
Contamination Heavy
100 hrs.
1,250 hrs.
5,000 hrs.
Mode No.
Setting Switch No.
Setting Position No.
Setting
10 (20)
1
01
Long-Life Filter
02
Ultra-Long-Life Filter (1)
03
—
Summary of Contents for REYQ72
Page 35: ...Specifications SiUS39 602 24 Specifications...
Page 121: ...Field Setting SiUS39 602 110 Test Operation...
Page 129: ...Troubleshooting by Remote Controller SiUS39 602 118 Troubleshooting...
Page 225: ...Troubleshooting OP Unified ON OFF Controller SiUS39 602 214 Troubleshooting...
Page 232: ...SiUS39 602 Piping Diagrams Appendix 221 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Page 235: ...Wiring Diagrams for Reference SiUS39 602 224 Appendix REYQ144 168 192MTJU C 3D050354A...
Page 240: ...SiUS39 602 Wiring Diagrams for Reference Appendix 229 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Page 249: ...Example of Connection R 410A Type SiUS39 602 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 602 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 602 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 602 iv Index...